Error Code Displayed Reason for error Possible remedy
e16 NO FUEL SERVO
The user has no servo in the current profile with one of
these names: FU1,FU2,GAS,OIL,CUP,PUM,WAS,PRI
Name one servo in current profile as a fuel servo
e17 INVALID SETPOINT
User has not configured setpoint 2 to be using
sensor 1
Configure setpoint 2 to use sensor 1
e18
Unused Unused
e19 SENSOR 1 MARGINAL SENSOR 1 has reached user defined marginal setting This could be normal operation
e20 SENSOR 1 MARGINAL SENSOR 1 has reached user defined marginal setting This could be normal operation
e21 SENSOR 2 MARGINAL SENSOR 2 has reached user defined marginal setting This could be normal operation
e22 SENSOR 2 MARGINAL SENSOR 2 has reached user defined marginal setting This could be normal operation
e23 SENSOR 2 MARGINAL SENSOR 2 has reached user defined marginal setting This could be normal operation
e24 SENSOR 3 MARGINAL SENSOR 3 has reached user defined marginal setting This could be normal operation
e25 SENSOR 3 MARGINAL SENSOR 3 has reached user defined marginal setting This could be normal operation
e26 SENSOR 3 MARGINAL SENSOR 3 has reached user defined marginal setting This could be normal operation
e27 SENSOR1 HIGH LIMIT SENSOR 1 has reached user defined limit setting This could be normal operation
e28 SENSOR1 HIGH LIMIT SENSOR 1 has reached user defined limit setting This could be normal operation
e29 SENSOR2 HIGH LIMIT SENSOR 2 has reached user defined limit setting This could be normal operation
e30 SENSOR2 HIGH LIMIT SENSOR 2 has reached user defined limit setting This could be normal operation
e31 SENSOR2 HIGH LIMIT SENSOR 2 has reached user defined limit setting This could be normal operation
e32 SENSOR3 HIGH LIMIT SENSOR 3 has reached user defined limit setting This could be normal operation
e33 SENSOR3 HIGH LIMIT SENSOR 3 has reached user defined limit setting This could be normal operation
e34 SENSOR3 HIGH LIMIT SENSOR 3 has reached user defined limit setting This could be normal operation
e35 SENSOR1 UNDER RNG SENSOR 1 input is under 2mA Defective sensor or check wiring
e36 SENSOR1 OVER RNG SENSOR 1 input is over 22mA Defective sensor or check wiring
e37 SENSOR2 UNDER RNG SENSOR 2 input is under 2mA Defective sensor or check wiring
e38 SENSOR2 OVER RNG SENSOR 2 input is over 22mA Defective sensor or check wiring
e39 SENSOR3 UNDER RNG SENSOR 3 input is under 2mA Defective sensor or check wiring
e40 SENSOR3 OVER RNG SENSOR 3 input is over 22mA Defective sensor or check wiring
e41
Z BOARD Z Board internal error Replace Z Board
e42
Z BOARD Z Board internal error Replace Z Board
e43
PPC4000 FAULT PPC4000 Internal Error Replace PPC4000 (notify Fireye about this error)
e44
PPC4000 FAULT PPC4000 Internal Error Replace PPC4000 (notify Fireye about this error)
e45
PPC4000 FAULT PPC4000 Internal Error Replace PPC4000 (notify Fireye about this error)
e46
O2 FAULT O2 Probe PPC4000 FAULT
Replace O2 Probe
e47 O2 FAULT O2 is not communicating with the PPC4000 Check Wiring or add 200 Ohm resistor
e48 O2 FAULT
O2 Probe is reporting that the O2 level is below the user
configured minimum
This could be normal operation
e49 O2 FAULT
O2 Probe is reporting that the O2 level is above the user
configured maximum
This could be normal operation