User`s guide

16
Terminal Type Description
Rating/wiring
P13.1 D1 10 Digital Input #10 120 VAC @ 1mA
P13.2 D1 9 Digital Input #9 120 VAC @ 1mA
P13.3 D1 8 Digital Input #8 120 VAC @ 1mA
P13.4 D1 7 Digital Input #7 120 VAC @ 1mA
P13.5 D1 6 Digital Input #6 120 VAC @ 1mA
P13.6 D1 5 Digital Input #5 120 VAC @ 1mA
P13.7 D1 4 Digital Input #4 120 VAC @ 1mA
P13.8 D1 3 Digital Input #3 120 VAC @ 1mA
P13.9 D1 2 Digital Input #2 120 VAC @ 1mA
P13.10 D1 1 Digital Input #1 120 VAC @ 1mA
P13.11 TBD Reserve 120 VAC @ 1mA
P13.12 TBD Reserve 120 VAC @ 1mA
P15.1 TBD 120 VAC @ 1mA
P15.2 Input HIGH, FSG High Purge Output 120 VAC @ 1mA
P15.3 Input LOW, FSG Low Fire Start 120 VAC @ 1mA
P15.4 Input AUTO, FSG Modulation Mode 120 VAC @ 1mA
P15.5 Input P4, Profile 4 Select 120 VAC @ 1mA
P15.6 Input P3, Profile 3 Select 120 VAC @ 1mA
P15.7 Input P2, Profile 2 Select 120 VAC @ 1mA
P15.8 Input P1, Profile 1 Select 120 VAC @ 1mA
P5.1 Output To FSG Low Fire Input (D) 120 VAC, 8A 250VAC
P5.2 Output To FSG Open Damper Input (8) 120 VAC, 8A 250VAC
P5.3 Output Aux Relay 1 120 VAC, 8A 250VAC
P5.4 Output Reserve 120 VAC, 16A 250VAC
P5.5 Output Reserve 120 VAC, 16A 250VAC
P5.6 Output Reserve 120 VAC, 16A 250VAC
P5.7 Output Reserve 120 VAC, 16A 250VAC
P5.8 Output Reserve 120 VAC, 16A 250VAC
P5.9 Output Safety Relay Output (P) 120 VAC, connect to non-recycle limits
P5.10 Output Safety Relay Input 120 VAC, connect to non-recycle limits
P14.1 Encoder Input (2)
P14.2 Encoder Input (1)
P14.3 4-20 mA IN (2) VFD (2) feedback
P14.4 4-20 mA IN (1) VFD (1) feedback
P14.5 4-20 mA OUT (2) VFD (2) drive
P14.6 4-20 mA OUT (1) VFD (1) drive
P14.7 - P14.12 Common Signal return
CAUTION: Ensure that electric power is turned off. Refer to SN-100 for
recommended grounding techniques.
Be aware that power to some interlocks (operating controls, air flow
switches, modulating circuits, etc.) may be derived from sources other
than what is controlling the PPC4000.