Datasheet

Publblicazione S201RCLP_1610_IT – Ottobre 2016
EXAMPLE
INSTALLATION EXAMPLE OF ROGOWSKI SENSOR
The material in this document is for information only and is subject to change without notice. While reasonable eorts have been made in the preparation of this document to assure
its accuracy, SENECA assumes no liability resulting from errors or omissions, or from the use of the information contained herein. Reproduction is forbidden unless authorized.
Via Austria, 26 • 35127 Padova - (I) - Tel. +39 049 87.05.359
Fax +39 049 87.06.287 • www.seneca.it • info@seneca.it
S201RC-LP
ROGOWSKI SENSORS CONVERTER LOOP-POWERED
ORDER CODES
Code Description
S201RC-LP
Loop-powered converter for ac current with Rogowski sensors
RC150-025-100-3M
Rogowski coil L=25cm Øint. 8cm,100mV/1kA-50Hz,cable L=3mt.
RC150-035-100-3M
Rogowski coil L=35cm Øint.11cm,100mV/1kA-50Hz,cable L=3mt.
RC150-040-100-3M
Rogowski coil L=40cm Øint.12cm,100mV/1kA-50Hz,cable L=3mt.
RC150-060-100-3M
Rogowski coil L=60cm Øint.19cm,100mV/1kA-50Hz,cable L=3mt.
RC150-090-100-3M
Rogowski coil L=90cm Øint.28cm,100mV/1kA-50Hz,cable L=3mt.
RC150-120-100-3M
Rogowski coil L=120cm Øint.38cm,100mV/1kA-50Hz,cable L=3mt.
RC150-180-100-3M
Rogowski coil L=180cm Øint.57cm,100mV/1kA-50Hz,cable L=3mt.
RC150-CAVEX-ROG1
Extending 1mt beyond the 3 mt. Standard cable connecting the
Rogowski coil L.1
RC150-CAVEX-ROG2
Extending 1mt beyond the 3 mt. Standard cable connecting the
Rogowski coil L.2
RC150-CAVEX-ROG3
Extending 1mt beyond the 3 mt. Standard cable connecting the
Rogowski coil L.3
TECHNICAL FEATURES
GENERAL DATA
Power supply
by output current loop 4..20 mA
Max consumption
< 0,6 W
Degree protection
IP20
Status indicator
Over alarm range
Response time
500 ms
Accuracy
0.5%
Thermal coefcient
<200 ppm/°C
Settings
Full scale and lter
Operating temperature
-25..70°C
Storage temperature
-40..85°C
Humidity
10 - 90 % (non-condensing)
Altitude
Up to 2000 m above s.l.
Dimensions LxHxD
18x110x62 mm
Connections
Removable terminal 5mm pitch (conductor
section 2.5 mm2)
Enclosure
PC-ABS self-extinguishing, grey color
Mounting
DIN rail 35 mm (IEC/EN 60715)
Standards
CE
Norms
EN61326 (EMC), EN61010-1 (SAFETY)
INPUT DATA
Channel
1
Type
Rogowski’s sensor 100mV / kA scales: 250A,
500A, 1000A, 2000A, 4000A (50-60Hz)
Rogowski’s sensor 333mV / kA scales: 75A,
150A, 300A, 600A, 1200A (50-60Hz)
Measurement: TRMS
Bandwidth 3kHz
Overload 20kA (2 Vrms)
Mains filter damping: Fast = 0.5s or Slow = 1s
DATI DI USCITA
Channel
1
Type
CURRENT
4 . . 2 0 m A
Max output: 22 mA
Power supply: by current loop 4..20 mA (9..28
Vdc)
Max load: 600 Ohm
Electric
motor
4..20mA
PLC
Rogowski coil
S201RC-LP
S201RC-LP
S201RC-LP
Rogowski coil
Rogowski coil
AC
main
power
METER
S2
S1
P
3
4
1 2
S201RC-LP
S
SENECA
2
1
0
9
8
7
6
5
4
3
S201RC-LP
S
SENECA
2
1
0
9
8
7
6
5
4
3
S201RC-LP
S
SENECA
2
1
0
9
8
7
6
5
4
3