GENERAL SPECIFICATIONS
from 25 to 180 cm (RC150)
a bayonet holder
from 150 to 500 g
thermoplastic UL94-V0
IP67
-30°C..+80°C
ELECTRICAL SPECIFICATIONS
100 mV / 1 kA @50Hz (standard) (RC150)
from 70 to 900 1(RC150)
better than ±1% of reading (with 15 mm diameter cable)
approx 40 Hz a 20 kHz
1000 VRMS CAT III, 600 VRMS CAT IV, pollution degree 2
7400 VRMS / 1 min
STANDARDS
APPROVALS CE
NORMS EN61010-1, EN61010-031, EN61010-2-031, EN61010-2-
032
ORDER CODES
Codes
Models
RC150-025-100-300
RC150-035-100-300
RC150-040-100-300
RC150-060-100-300
RC150-090-100-300
RC150-120-100-300
RC150-180-100-300
RC190-030-333-300
RC190-035-333-300
RC190-060-333-300
RC190-090-333-300
RC190-120-333-300
RC190-180-333-300
from 30 to 180 cm (RC190)
from 8 ±0.2 mm to 57 mm (RC150)
from 12 ±0.2 mm to 57 mm (RC190)
333 mV / 1 kA @50Hz (standard) (RC190)
from 300 to 2000 1(RC190)
Rogowski coils have been used for the detection and measurement of electric currents for decades. They are based on a
simple principle: an “air-cored” coil is placed around the conductor in a toroidal fashion and the magnetic field produced
by the current induces a voltage in the coil. The voltage output is proportional to the rate of change of current. This voltage
is integrated, thus producing an output proportional to the current.
By using precision winding techniques, especially developed for the purpose, the coils are manufactured so that their
output is not influenced by the position of the conductor within the toroid, and to reject interference from external
magnetic fields caused, for example, from nearby conductors. Basically, a Rogowski coil current measuring system
consists of a combination of a coil and conditioning electronics. Rogowski coil current transducers are used for the AC
measurement.
What is a Rogowski coil?
Coil length
Coil diameter
Fastening
Weight
Material
Protection degree
Operating temperature
Output level (RMS)
Coil resistance
Accuracy
Frequency range
Working voltage
Test voltage
GENERAL DATA
Description
RC150 versions (color yellow)
Rogowski coil with coil lenght 25cm and 100mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 35cm and 100mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 40cm and 100mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 60cm and 100mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 90cm and 100mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 120cm and 100mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 180cm and 100mV/1kA output - 300cm cable lenght
RC190 versions (color red)
Rogowski coil with coil lenght 30cm and 333mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 45cm and 333mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 60cm and 333mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 90cm and 333mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 120cm and 333mV/1kA output - 300cm cable lenght
Rogowski coil with coil lenght 180cm and 333mV/1kA output - 300cm cable lenght