Datasheet
via Germania, 34 • 35127 Padova - (I) - Tel. +39 049 87.05.359 (.408)
Fax +39 049 87.06.287 • www.seneca.it • info@seneca.it
K121_1103_EN –
Document subject to modications and revisions. Reproduction forbidden if not authorized.
TECHNICAL dATA
SCHEMES, PROGRAMMING
COdICI d’ORdINE
Model K121
Programmable Loop-Powered Universal
Converter
Programming
Kit
S117P1
Easy-LP software + USB adapter
K121
Converters / Isolators 6,2 m housing
K LINE
TABLE OF INPUT RANGE
CONFIGURATION
EASY-LP SOFTWARE SCREENSHOTS
Programmable
Loop-Powered Universal
Converter
S117P1 K121
Power supply
7..30 Vdc
Universal Input
Thermocouple (J,K,R,S,T,B,E,N) - RTD (PT100-500-1000-Ni100) with 2,3,4 wire connections
Voltage -150…+150mV, -30…+30V - Current -24…+24mA
Potentiometer 500 Ω -10 KΩ - Resistance up to 1760 Ω
Output
4..20 mA (loop powered)
Galvanic isolation
1,5 kVac
Configuration
Through EASY-LP software (S117p) Via free software
Operating temperature
-20..+65 °C
Settings
EASY-LP by USB adapater (S1117P1, free custom linearization
Dimension (wxhxd)
6.2x93.1x102.5 mm
Connection
Spring clamp (EN 60175)
Approvald & Norms
CE, EN 61000-6-4, EN 64000-6-2, EN 61010-1
4..20 mA
PLC with active input
Input
Voltage
7..30 Vdc
-
+
Thermocouple
(J,K,R,S,T,B,E,N), EN 60584
RTD (Pt100, Pt500, Pt1000,
Ni100) 2/3/4 wires
Potentiometer
500 Ω -10 KΩ
Sensors /
Transducers
Level
Flow
Pressure
Volume
Humidity
Speed
Acceleration
Force
…
mV
mA
Ω
V
INPUT OUTPUT / POWER SUPPLY