Technical data
Configuring Messages
16.9 Configuring the 'Reporting of System Errors'
Programming with STEP 7
390 Manual, 05/2010, A5E02789666-01
16.9.8 Assignment of System Errors to Error Classes
The following table shows the system errors and their error classes:
Hardware Error Error class
Central
Rack Failure Rack error
Power supply module / CPU Power supply error - *
H CPU Redundancy loss - *
Redundancy reintegration - *
Module
Plug/pull of the module or wrong
module type Module error
Data record 0 Module error
Channel error Channel error
DP master Failure Rack error
IO controller Failure Rack error
AS i master Failure Rack error
PROFIBUS DP
DP station Failure Rack error
Manufacturer-specific diagnostics - *
Head Manufacturer-specific diagnostics - *
Module
Plug/pull of the module or wrong
module type
Module error
Data record 0 Module error
Channel error Channel error
Diag. rep. head
Specific errors of the diagnostic
repeater - *
Head ET 200 B, C, U, Eco Faulty Module error
H station Failure Rack error
Head H station Redundancy loss - *
PROFINET IO
IO device Failure Rack error
IO device head module Manufacturer-specific error - *
Channel error Channel error
Maintenance - *
Data record 0 Module error
Channel error for the entire head
module (Subslot = 0) Module error
IO device head submodule (PDEV) Channel error Channel error
Maintenance - *
Data record 0 Module error
Channel error for the entire head
submodule (Subslot = 0)
Submodule error