Technical data
Configuring Messages
16.9 Configuring the 'Reporting of System Errors'
Programming with STEP 7
Manual, 05/2010, A5E02789666-01 387
ATTENTION
Please note the following:
• The CPU no longer goes into STOP mode when Report System Error generates OB85 upon
the error event Error While Updating Process Image.
• OB85 is also called up by the CPU when the following errors occur:
- "Error event for an OB that is not loaded"
- "Error when calling or accessing an OB that Is not loaded"
When these errors occur, the CPU still goes into STOP mode when Report System Error
generates OB85, as was the case before Report System Error was in use.
• The setting "CPU goes into STOP mode after executing diagnostic FB" is NOT effective for
OB84 and OB85, because the FB of Report System Error is not called up in these OBs. In the
case of OB85, this setting is noted indirectly by the FB call in OB83.