Technical data

Configuring Messages
16.9 Configuring the 'Reporting of System Errors'
Programming with STEP 7
Manual, 05/2010, A5E02789666-01 381
Note
The station errors (failure/return) are displayed in plain text for all PROFIBUS DP slaves.
The manufacturer-specific diagnostics is supported for all PROFIBUS DP slaves with the following
restrictions:
- Only V1 slaves are supported. These are slaves with a GSD file containing the entry
"DPV1_Slave=1".
- The DP interrupt mode must be set to "DPV0" for this slave.
Errors that do not occur during operation (CPU in STOP, DP slave failed):
Station errors are supported
Module errors are supported
Channel errors are supported and extended channel error information is evaluated
In STEP 7 the diagnostics message is displayed via the call of the module state in the on-line
window "HW Config" (diagnose hardware) in the "DP Slave Diagnostics" tab card under "Hex
display".
Diagnostic Repeater: The messages of the Diagnostic Repeater are output as plain text in DPV0
mode. The text is read from the GSD file.
PROFIBUS DP over IE/PB Link or IWLAN/PB Link
The PROFIBUS DP master system of an IE/PB link cannot be diagnosed.
For a PROFIBUS DP master system downstream from an IE/PB link, the status is not updated
in the PROFIBUS data block (DB 125). The diagnostics is partially performed via the
PROFINET IO-DB. In this case, only the status of the slaves (OK, disrupted, failed) in the
PROFINET IO DB is available, not the module and channel errors.
PROFIBUS DP/PA via DP/PA-Link
The following station statuses are detected:
Station OK (the entire station is working properly)
Station disrupted (an error occurred on the station, but it is continuing to run)
Station failed (the entire station has failed)
Note
You cannot configure the DP/PA Link using a GSD file.
Diagnostics of a DP/PA Link with a 300 series CPU is not supported.