Technical data

Technical data
Powador 2002 | 3002 | 4202 | 5002 | 6002
Electrical data 2002 3002
Input variables
Max. recommended PV generator power 2 000 W 3 000 W
MPP range 125 V … 510 V 200 V … 510 V
No-load voltage 600 V* 600 V*
Max. input current 14.3 A 13.5 A
Number of strings 3 3
Number of MPP trackers 1 1
Inverse polarity protection short-circuit diode short-circuit diode
Output variables
Rated output 1 650 VA 2 500 VA
Max. output 1 650 VA 2 500 VA
Supply voltage acc. to local requirements acc. to local requirements
Rated current 7.2 A 10.9 A
Rated frequency 50 Hz / 60 Hz 50 Hz / 60 Hz
cos phi 0.80 inductive ... 0.80 capacitive 0.80 inductive ... 0.80 capacitive
Number of grid phases 1 1
General electrical data
Max. effi ciency 95.9 % 96.0 %
European effi ciency 95.3% 95.4 %
Night consumption 0.4 W 0.4 W
Switching plan self-commutated, galvanically isolated,
HF transformer
self-commutated, galvanically isolated,
HF transformer
Network monitoring acc. to local requirements acc. to local requirements
Mechanical data
Display LCD 2 x 16 characters, LED LCD 2 x 16 characters, LED
Control units 2 buttons for display control 2 buttons for display control
Interfaces RS485, S0 RS485, S0
Fault signalling relay potential-free NOC max. DC 30V / 3A
max. AC 250 V / 1.5 A
potential-free NOC max. DC 30V / 3A
max. AC 250 V / 1.5 A
Connections PCB terminals inside the unit (max. cross section. 6 mm² exible),
Cable connection via cable fi ttings (DC: solar connector, AC fi tting M32 and terminal)
Ambient temperature -20 °C … +60 °C** -20 °C … +60 °C**
Cooling free convection / no fan free convection / no fan
Protection class IP54 IP54
Noise emission < 35dB (A) (noiseless) < 35dB (A) (noiseless)
DC switch integrated integrated
Casing aluminium aluminium
H x W x D 450 x 340 x 200 mm 500 x 340 x 200 mm
Weight 14.5 kg 20 kg
4202 5002 6002
4 200 W 5 000 W 6 000 W
200 V … 510 V 200 V … 510 V 200 V … 510 V
600 V* 600 V* 600 V*
18.5 A 22.4 A 26.5 A
3 3 3
1 1 1
short-circuit diode short-circuit diode short-circuit diode
3 500 VA 4 200 VA 5 000 VA (Germany: 4600 VA)
3 500 VA 4 200 VA 5 000 VA
acc. to local requirements acc. to local requirements acc. to local requirements
15.2 A 18.3 A 21.7 A (Germany: 20.0 A)
50 Hz / 60 Hz 50 Hz / 60 Hz 50 Hz / 60 Hz
0.80 inductive ... 0.80 capacitive 0.80 inductive ... 0.80 capacitive 0.80 inductive ... 0.80 capacitive
1 1 1
95.9 % 95.9 % 95.9 %
95.1 % 95.3 % 95.3 %
0.4 W 0.4 W 0.4 W
self-commutated, galvanically isolated,
HF transformer
self-commutated, galvanically isolated,
HF transformer
self-commutated, galvanically isolated,
HF transformer
acc. to local requirements acc. to local requirements acc. to local requirements
LCD 2 x 16 characters, LED LCD 2 x 16 characters, LED LCD 2 x 16 characters, LED
2 buttons for display control 2 buttons for display control 2 buttons for display control
RS485, S0 RS485, S0 RS485, S0
potential-free NOC max. DC 30V / 3A
max. AC 250 V / 1.5 A
potential-free NOC max. DC 30V / 3A
max. AC 250 V / 1.5 A
potential-free NOC max. DC 30V / 3A
max. AC 250 V / 1,5 A
PCB terminals inside the unit (max. cross section. 6 mm² exible, 10 mm² rigid),
Cable connection via cable fi ttings (DC: solar connector, AC fi tting M32 and terminal)
-25 °C … +60 °C** -25 °C … +60 °C** -25 °C … +60 °C**
free convection / no fan fan fan
IP54 IP54 IP54
< 35dB (A) (noiseless) < 45dB (A) (fan) < 45dB (A) (fan)
integrated integrated integrated
aluminium aluminium aluminium
600 x 340 x 240 mm 600 x 340 x 240 mm 600 x 340 x 240 mm
26 kg 28 kg 28 kg
Applicable standards and regulations are taken into account for each country version that is set.
*To protect the hardware, the inverter starts up only at voltages < 550V
**Power derating at high ambient temperatures
Applicable standards and regulations are taken into account for each country version that is set.
*To protect the hardware, the inverter starts up only at voltages < 550V
**Power derating at high ambient temperatures
41