Datasheet

ESG 5.15
3-phase voltage monitoring relay
EMR DU31D
Technical data
Nominal voltage 3(N) ~400/230 V, 9 VA / 2 W
Nominal frequency 48 ... 63 Hz
Drop-out voltage >20% of the nominal voltage
Recovery time 500 ms
Measuring circuit: Input:
3(N) ~400/230 V terminals (N)-L1-L2-L3 (= supply voltage)
Overload capacity:
3(N) ~400/230 V -30% ... +30%
Input resistance:
3(N) ~400/230 V according to nominal voltage 9 VA / 2 W
Asymmetry: fix circa 30%
Type key
Construction
D Industrial design 22.5 mm
S pluggable 11 poles
Function
U Voltage
I Current
P CosPhi
T Temperature
S Star-Delta
Measuring circuit
A No measuring circuit I 12 Vdc
B 3(N)~115/66 Vac J 24 Vdc
C 3(N)~230/132 Vac K 36 Vdc
D 3(N)~400/230 Vac L 48 Vdc
E 1 30/60/300 Vac/dc M 1~110 Vac
F 1 100mA/1A/10A ac/dc N 1~230 Vac
G PTC O 1 A
H CosPhi P 5 A
Output
1 1 changer
2 2 changers
3 1 NC contact / 1 NO contact
Special functions
1 = Additional asymmetry monitoring
Connecting voltage
1 Measuring circuit
2 24...240 Vac/dc
3 230 Vac
S U 3 1 D ...EMR