Datasheet
ESG 5.14
3-phase voltage monitoring relay
EMR SU31D
Functions
Monitoring of phase sequence, phase failure and detection of return
voltage (by means of evaluating the asymmetry).
• Voltage monitoring in 3-phase mains
• Measuring range 400/230 Vac 3Ph
• Monitoring of phase sequence and phase failure
• Detection of reverse voltage
• Connection of neutral wire optional
• 2 changers
Reference data
Selectron
®
EMR Article no.
SU31D 400/230 Vac 3Ph 41230019
(Order data see chapter 1)
Connecting voltages
3(N) ~400/230 V, Terminals (N)-L1-L2-L3 (= supply voltage)
100% duration of operation
Indicators
Green LED ON: indication of supply voltage
Yellow LED ON/OFF: indication of relay output
Output relay
1 NC contact / 1 NO contact
Rated voltage: 250 Vac
Switching capacity: 1250 VA (5 A / 250 Vac)
Fusing: 5A fast acting