Datasheet
ESG 7.10
3-phase voltage monitoring relay
EMR IU11D1, IU21D1
Functions
Monitoring of phase sequence, phase failure and monitoring of
asymmetry with adjustable asymmetry.
• Voltage monitoring in 3-phase mains
• Measuring range 400/230 Vac 3Ph
• Monitoring of phase sequence and phase failure
• Monitoring of asymmetry
• Connection of neutral wire optional
• 1 or 2 change-over contacts
Reference data
Selectron
®
EMR Article no.
IU11D1 41230030
IU21D1 41230031
(Order data see chapter 1)
Connecting voltages
3(N) ~400/230 V, Terminals (N)-L1-L2-L3 (= supply voltage)
-30% ... +30% of U
N
100% duration of operation
Indicators
Green LED ON: indication of supply voltage
Yellow LED ON/OFF: indication of relay output
Output relay
1 or 2 potential free change-over contact(s)
Rated voltage: 250 Vac
Switching capacity: 1250 VA (5 A / 250 Vac)
Fusing: 5A fast acting
EMR IU11D1
EMR IU21D1