Datasheet

ESG 7.15
1-phase or 3-phase voltage monitoring relay
(Multifunction)
EMR IU11D
Technical data
Nominal consumption 3(N) ~400/230 V, 8 VA / 1 W
Nominal frequency 48 ... 63 Hz
Drop-out voltage >20% of the supply voltage
Base accuracy ±5% (of scale limit)
Adjustment accuracy ±5% (of scale limit)
Repetition accuracy 2%
Temperature influence 1% / °C
Recovery time 500 ms
Measuring circuit: Input:
3(N) ~230/400 V Terminals (N)-L1-L2-L3
Overload capacity:
3(N) ~230/400 V -30% ... +30%
Input resistance:
3(N) ~230/400 V according to nominal voltage 8 VA / 1 W
Switching threshold:
Max: 80% ... 130% of U
N
Min: 70% ... 120% of U
N
Type key
Construction
D Industrial design 22.5 mm
S pluggable 11 poles
I Mounting position 22.5/35 mm
Function
U Voltage
I Current
P CosPhi
T Temperature
S Star-Delta
Measuring circuit
A No measuring circuit I 12 Vdc
B 3(N)~115/66 Vac J 24 Vdc
C 3(N)~230/132 Vac K 36 Vdc
D 3(N)~400/230 Vac L 48 Vdc
E 1 30/60/300 Vac/dc M 1~110 Vac
F 1 100mA/1A/10A ac/dc N 1~230 Vac
G PTC O 1 A
H CosPhi P 5 A
Q 10 A
Output
1 1 changer
2 2 changers
3 1 NC contact / 1 NO contact
Special functions
1 = Additional asymmetry monitoring
Connecting voltage
1 Measuring circuit
2 24...240 Vac/dc
3 230 Vac
IU1 1 D ...EMR