Datasheet

ESG 7.14
Indicators
Red LED ON/OFF: indication of failure of the
corresponding threshold
Red LED flashes: indication of tripping delay
of the corresponding threshold
Yellow LED ON/OFF: indication of relay output
Time ranges
Start-up suppression time: -
Tripping delay: Adjustment range 0.1 ... 10 s
1-phase or 3-phase voltage monitoring relay
(Multifunction)
EMR IU11D
Functions
Voltage monitoring in 1-phase and 3-phase mains with adjustable
thresholds, adjustable tripping delay, monitoring of phase sequence
and phase failure and the following functions which are selectable by
means of rotary switch.
- Undervoltage monitoring
- Undervoltage monitoring and monitoring of phase sequence
- Monitoring of window between Min and Max
- Monitoring the window between Min and Max and monitoring
of phase sequence.
Voltage monitoring in 3-phase mains
Measuring range 400/230 Vac 3Ph / 230 V 1Ph
Multifunction
Monitoring of phase sequence and phase failure
Connection of neutral wire optional
1 change-over contact
Reference data
Selectron
®
EMR Article no.
IU11D 41230032
(Order data see chapter 1)
Connecting voltages
1(N) ~ 230 V, terminals (N)-L1-L2-L3 (= Measuring voltage)
3(N) ~ 400/230 V, terminals (N)-L1-L2-L3 (= Measuring voltage)
-30% ... +30% of U
N
100% duration of operation
Output relay
1 potential free change-over contact
Rated voltage: 250 Vac
Switching capacity: 1250 VA (5 A / 250 Vac)
Fusing: 5A fast acting
EMR IU11D