ESG 6.10
3-phase voltage monitoring relay
EMR DU21D
Functions
Monitoring of phase sequence, phase failure and detection of return
voltage (by means of evaluating the asymmetry).
• Voltage monitoring in 3-phase mains
• Measuring range 230 ... 400 Vac 3Ph
• Monitoring of phase sequence and phase failure
• Detection of reverse voltage
• Connection of neutral wire optional
• 2 changers
Reference data
Selectron
®
EMR Article no.
DU21D 230 ... 400 Vac 3Ph 41230001
(Order data see chapter 1)
Connecting voltages
3(N) ~230/400 V, Terminals (N)-L1-L2-L3 (= supply voltage)
Tolerance: 3(N) ~230/400 V, 3(N) ~342 ... 457 V
Indicators
Green LED ON: indication of supply voltage
Yellow LED ON/OFF: indication of relay output
Output relay
2 potential free change-over contacts
Rated voltage: 250 Vac
Switching capacity (distance <5 mm): 750 VA (3 A / 250 Vac)
Switching capacity (distance >5 mm): 1250 VA (5 A / 250 Vac)
Fusing: 5A fast acting
Time ranges
Start-up suppression time: max. 500 ms
Tripping delay: max. 350 ms