Datasheet
ESG 6.32
Mechanical data
Housings in self-extinguishing plastic material. Protection mode IP 40
Mounting: snapping mode: Fixing on profile rail according DIN 46277/3 (EN 50 022)
Connection via contact protected terminals up to 4 mm
2
, protecting mode IP 20
Environmental conditions
Admissible environmental temperatures from -25 ºC ... +55 ºC (corresponds IEC 68-1)
Storage and transport temperature from -25 ºC ... +70 ºC
Application class IEC 721-3-3 (EN 60721-3-3)
Output relay
Electrical lifetime: 230 Vac, min. 2x10
5
switching cycles at 1000 VA ohmic load.
Mechanical lifetime: min. 20 x 10
6
switching cycles
Contact material AgNi
Frequency range 48 ... 400 Hz / 24 ... 240 Vac, 16 ... 48 Hz / 24 ... 48 Vac
Duration of operation 100%
Protection
Protection of the unit 5 A fast
Terminals
Contact protection according VDE 0106 and VBG 4
Terminal type: sleeve with indirect screw pressure
Wire to connect: rigid or flexible
Connecting limit: 4 mm
2
Terminal variants: 1 wire 0,5 mm
2
... 2,5 mm
2
with/without wire end covers
1 wire 4 mm
2
without wire end covers
2 wires 0,5 mm
2
... 1,5 mm
2
with/without wire end covers
2 wires 2,5 mm
2
flexible without wire end covers
max. screw in torque: 1,0 Nm
Terminal screw for screw driver with PZ-1
Insulation
Isolation nominal voltage: 250 Vac (corresponds to IEC 60664-1)
Rating surge voltage: 4 kV, over-voltage category III, corresponds to IEC 60664-1
Electromagnetic compatibility
Electrostatic discharge: Level 3, 6 kV contact, 8 kV air (corresponds to IEC 1000-4-2)
High frequency electromagnetic fields: Level 3, 10 V/m (corresponds to IEC 1000-4-3)
Fast transients: Level 4, 4 kV / 2,5 kHz, 5/50 ns (corresponds to IEC 1000-4-4)
Lightning discharge: Level 3, 2 kV com., 1 kV dif., (corresponds to IEC 1000-4-5
Cable running disturbances inducted by HF fields: Level 3, 10 V RMS (corresponds to IEC 1000-4-6)
Spurious radiation net and aerial network: Class B (corresponds to CISPR 22)
Prescriptions
Air and leakage paces: VDE 0110iGr. C/250
Test voltage: VDE 0435 2000Vac
Low voltage directions according to IEC 664-1
EMC emissions: EN 50 081-1 and EN 55 022 class B
EMC interference stability: Voltage impact strength according to IEC 1000-4-5
Burst: EN 50 082-2, EN 61 812-1 (level 3)
ESD: IEC 1000-4-2
HF over metallic circuits: EN 50 082-2, ENPr 50141
Electro magnetic HF field according to EN 50 082-2, ENPr 50140 and ENPr 50204
Production standard: according to ISO 9001
Prescriptions and standards