Datasheet

ESG 6.26
Indicators
Green LED ON: indication of supply voltage
Green LED flashes: indication of ON-Delay
Red LED Max/Min ON/OFF: indication of failure of the
corresponding threshold
Red LED Max/Min flashes: indication of tripping delay of the
corresponding thereshold
Red LED UFailure ON/OFF: voltage failure
Yellow LED ON/OFF: indication of relay output
Time ranges
On-Delay:: Adjustment range 0 ... 10 s
Tripping delay: Adjustment range 0.1 ... 10 s
Frequency monitoring relay for 50/60 Hz
power grids
EMR DF22Q
Functions
Frequency monitoring for 50/60Hz power grids with adjustable thre-
sholds, timing for ON-Delay and tripping delay separately adjustable
and the following functions which are selected by means of rotary switch:
Nominal frequency 50Hz:
WIN 50Hz
- Monitoring the window between Min and Max
WIN+LATCH 50Hz
- Monitoring the window between Min and Max with fault latch
Nominal frequency 60Hz:
WIN 60Hz
- Monitoring the window between Min and Max
WIN+LATCH 60Hz
- Monitoring the window between Min and Max with fault latch
Fault latch
Power failure detection
Measuring range 110 ... 400 Vac
Windowifunction
Adjustable thresholds
2 changers
Reference data
Selectron
®
EMR Article no.
DF22Q 110 ... 400 Vac 41230040
(Order data see chapter 1)
Connecting voltages
24 ... 240 Vac/dc, Terminals A1-A2 (galvanically separated)
Tolerance: 24 ... 240 Vdc, -20% ... +25% (galvanically separated)
24 ... 240 Vac, -15% ... +10% (galvanically separated)
100% duration of operation
Output relay
2 potential free change-over contacts
Rated voltage: 250 Vac
Switching capacitiy: 750 VA (3A / 250 VAC)
- If the distance between the devices is less than 5mm!
Switching capacity: 1250 VA (5A / 250 VAC)
- If the distance between the devices is greater than 5mm!
Fusing: 5A fast acting
EMR DF22Q