Test Report
Report Reference No.: 50337286 001
UL 1012
Clause
Requirement – Test
Result – Remark
Verdict
Page 55 of 75
61.2.19
With reference to 23.3.2, a unit that relies on the installing
electrician to maintain the 1/4 inch (6.4 mm) spacing associated
with Class 2 or Class 3 conductors shall be marked with the
following or equivalent: "Dress ___ circuits at least 1/4 inch
away from ___ circuits," where the blanks are to be completed
appropriately with power, light, or Class 1 and Class 2 or Class
3, respectively.
N/A
61.2.20
A power unit not furnished with a detachable power supply cord
as described in the Exceptions to 12.3.1 and 12.3.7 shall be
marked adjacent to the appliance coupler to inform the user to
see the instruction manual (see 61.1.10) for proper selection of
the power supply cord.
N/A
Exception: The marking may be in the form of a tag,
nonpermanent label, or product insert that is provided on or
packaged with the unit so that the marking is visible at the time
of installation.
N/A
61.2.21
In accordance with 12.3.8, a power unit intended for use by
travelers shall be marked with the following or equivalent:
Not used for traverlers
N/A
a) "See instruction manual for use in countries other than the
U.S.A. ";
N/A
b) “See instructions for input voltage conversion”; or
N/A
c) “See instructions if the input plug does not fit the power
outlet.”
N/A
61.2.22
In accordance with 7.7.1, individual modules of a modular
power unit shall be marked with:
N/A
a) Information identifying the module consistent with its
function in the assembled system, such as "voltage regulation
section of Model XYZ POWER SUPPLY"; and
N/A
b) A reference to the installation instructions.
N/A
The marking may be in the form of a paper tag or any other
nonpermanent material. See 62.1.11.
N/A
61.3
Application
P
61.3.1
Unless stated otherwise, markings required by this Standard
shall be permanent. A permanent marking shall be molded, die-
stamped, paint-stenciled; stamped or etched metal that is
permanently secured; or indelibly stamped on a pressure-
sensitive label secured by adhesive. The marking means shall
comply with the Standard for Marking and Labeling
Systems, UL 969. Ordinary usage, handling, storage, and the
like of the unit are to be considered in determining whether a
marking is permanent.
P
62
Instructions
P
62.1
General
N/A
62.1.1
Instructions for mounting shall be furnished with each power
unit intended for permanent mounting.
N/A
62.1.2
A commercial stationary or fixed power unit that exceeds the
temperature limits specified in Table 42.1 [see footnote (k) to
Table 42.1] shall be provided with instructions specifying that
"The power unit is to be installed so that it is not likely to be
contacted by people " or equivalent wording.
N/A