Produkte Products Prüfbericht - Nr.: Test Report No.: 50337286 001 Seite 1 von 75 Page 1 of 75 Auftraggeber: Client: FSP-POWERLAND TECHNOLOGY INC 12F Building A, No.6 Yongzhi Road, Qinhuai District, Nanjing Jiangsu, China, 210014. Gegenstand der Prüfung: LI-ION BATTERY CHARGER Test item: Bezeichnung: Identification: Wareneingangs-Nr.: Receipt No.: Refer to Electrical rating table Serien-Nr.: Serial No.
Report Reference No.: 50337286 001 TEST REPORT UL 1012 & CSA C22.2 No. 107.1 Power Units Other Than Class 2 & Power Conversion Equipment Report Reference No ..................... : See cover page Tested by (printed name and signature) .......... : See cover page Approved by (printed name and signature) .......... : See cover page Date of issue ................................... : See cover page Testing Laboratory Name ............. : See cover page Address ...........................................
Report Reference No.: 50337286 001 Copy of marking plate: Remark: 1. For warning markings: the height of the letters in the word “CAUTION”, “DANGER” shall be no less than 1/8 inch (3.2 mm) and the height of the remaining letters shall be no less than 1/16 inch (1.6 mm). 2. Manufacture date information included in S/N. Digits “XXXX” after DC: the first XX means final 2 numbers of year, the second XX means weeks, for example 2009 means the 9th weeks of year 2020. 3. FCC/ICES was not evaluated in this report.
Report Reference No.: 50337286 001 Instructions: Note: 1. The height of lettering in the text and illustrations of the safety instructions shall be as follows: a) Upper case letters shall be not less than 1/12 inch (2.1 mm) in height; b) Lower case letters shall be not less than 1/16 inch (1.6 mm) in height; c) The phrases “IMPORTANT SAFEGUARDS” and “SAVE THESE INSTRUCTIONS” shall be in letters no less than 3/16 inch (4.8 mm) in height. 2. French translation shall be provided for Canada market.
Report Reference No.: 50337286 001 Summary of testing: Model NB-58D8-5D0 was tested and fulfilled the test specifications. The tested model was complied with the test standard UL 1012 and C22.2 No. 107.1. The report is only evaluated the device intended to use in non- hazard location.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 7 Frame and Enclosure General A power unit shall be formed and assembled so that it has the strength and rigidity necessary to resist the abuses to which it is subjected, without increasing the risk of fire, electric shock, or injury to persons due to total or partial collapse which results in a reduction of spacings, loosening or displacement of parts, or other serious defects.
Report Reference No.: 50337286 001 UL 1012 Clause 7.1.9 7.1.10 7.1.11 7.1.12 7.1.13 7.2 Requirement – Test Result – Remark a) Have a flammability classification of V-1 or better in accordance with the Standard for Tests for Flammability of Plastic Materials for Parts in Devices and Appliances, UL 94; and b) Comply with the requirements for physical barriers specified in the Standard for Polymeric Materials - Use in Electrical Equipment Evaluations, UL 746C. The requirement in 7.1.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 7.2.1 A power unit intended to be fastened in place shall have a means for securely mounting it in position. Bolts, screws, and other parts used for mounting the power unit shall be independent of those used for securing components. A portable power unit intended for wall mounting shall employ a keyhole slot or the equivalent as a mounting means.
Report Reference No.: 50337286 001 UL 1012 Clause 7.5 7.5.1 7.5.2 7.6 7.6.1 7.6.2 7.6.3 7.6.4 7.6.5 7.6.6 Requirement – Test Result – Remark Exception: Methods utilizing fusion techniques, such as solvent cementing, ultrasonic welding, electromagnetic induction, and thermal welding are not required to be investigated.
Report Reference No.: 50337286 001 UL 1012 Clause 7.6.7 7.6.8 7.7 7.7.1 8 8.1 8.2 8.3 8.4 Requirement – Test Result – Remark e) Creation of additional risks of injury such as pinch points during servicing, replacement of fuses, and maintenance. Exception: A commercial or power unit may be provided with a marking - in lieu of other means - located adjacent to the part being guarded, to instruct the user that the cover or guard should be replaced before intended operation of the power unit. See 61.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 8.5 An uninsulated live part that can cause electric shock shall be located or enclosed so that protection against unintentional contact is provided. 9 9.1 9.1.1 Protection of Service Personnel General These requirements apply to live parts used in circuits involving a risk of electric shock.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 9.2.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 10.2 A component such as a control switch, a lampholder, an attachment-plug receptacle, or a plug connector shall be mounted securely and shall be prevented from turning by means other than friction between surfaces. Exception No.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 12.1.
Report Reference No.: 50337286 001 UL 1012 Clause 12.2.6 12.2.7 12.2.8 12.2.9 12.2.10 12.2.11 Requirement – Test Result – Remark Exception No. 1: A No. 8 (4.2 mm diameter) screw may be used at a terminal intended only for the connection of a 14 AWG (2.1 mm2) conductor. Exception No. 2: A No. 6 (3.5 mm diameter) screw may be used for the connection of a 16 AWG (1.3 mm2) or 18 AWG (0.82 mm2) control-circuit conductor. A wire-binding screw shall thread into metal.
Report Reference No.: 50337286 001 UL 1012 Clause 12.2.12 12.2.13 12.3 12.3.1 12.3.2 12.3.3 12.3.4 12.3.5 Requirement – Test Result – Remark e) After installation of the pressure terminal connector in the intended manner, the power unit shall comply with the requirements in this standard. A terminal intended for connection of a grounded power supply conductor shall be made of or plated with metal substantially white in color and shall be readily distinguishable from other terminals.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 12.3.6 If a unit with a permanently attached power supply cord can be adapted for use on two or more different voltages by field alteration of internal connections, the attachment plug provided with the unit shall be of a type required for the voltage and current for which the unit is shipped from the factory. The power unit shall be provided with instructions as described in 62.1.4.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 12.4.3 If a knot in a flexible cord serves as strain relief, the surfaces No knot that the knot may touch shall be free from burrs, fins, sharp edges, and projections that can damage the cord.
Report Reference No.: 50337286 001 UL 1012 Clause 13.2 13.3 13.4 13.5 13.6 13.7 13.8 Requirement – Test Result – Remark d) A nonmetallic terminal cover is employed to reduce the UL recognized output likelihood of bridging between terminals. The cover shall be connector close-fitting over the top and all sides of the terminal block, with no opening other than those necessary for entry of conductors. The cover shall be attached so that it cannot be discarded.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 13.9 A connector for an output not exceeding 42.4 volts peak or 60 volts dc shall have no exposed current carrying pins that could be short-circuited when placed on a flat metal surface. A strain-relief means and a bushing for the output cord shall comply with the requirements in 12.4 and 12.5.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 14.7 Sections of a unit that are intended to be combined in field installations to form overall unified enclosures (modular units see 7.7.1) may be acceptable if the modules provide complete enclosures or the equivalent that facilitate the routing or interconnecting cables or other wiring from one unit of the system to another. Such constructions shall provide substantially complete enclosures for all wiring.
Report Reference No.: 50337286 001 UL 1012 Clause 16.3 16.4 16.5 16.6 16.7 16.8 16.9 Requirement – Test Result – Remark b) To become energized through an electrical fault. To determine if a part is likely to become energized, the following factors are to be evaluated: a) The proximity of wiring; b) The results of a dielectric voltage-withstand test after a test such as the overload or the endurance test; and c) The results of appropriate burnout tests.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 16.10 The grounding conductor shall be connected to the grounding Complied blade of a grounding attachment-plug and shall be connected to dead metal parts within the frame or enclosure by means such as a screw or stud, nut, and lockwasher. An external force applied to the power supply cord shall not transmit stress to the grounding connection on the frame or enclosure before the linevoltage connections are broken.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 17.1.4 In addition to the parts mentioned in 17.1.3, other parts not required to be bonded are small internal assembly screws, rivets, or other small fasteners, a handle for a disconnect switch, and a relay or contactor magnet and armature.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 18.1 A unit rated as follows shall have the grounded conductor connected to the components, when provided, and as specified in 18.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test Result – Remark Verdict a) A barrier is provided between the connector and the opening; or b) Drawings are provided specifying that the conductors are not to enter or leave the enclosure directly opposite the wire connector. See Illustrations A, B, and C of Figure 19.1. When a conductor is restricted by a barrier or other means from being bent where it leaves the connector, the distance shall be measured from the end of the barrier.
Report Reference No.: 50337286 001 UL 1012 Clause 20.3 20.4 20.5 20.6 Requirement – Test Result – Remark a) The circuit has no electrical connection, including a solidly connected grounded circuit conductor, to supply conductors originating in another wiring system; b) The circuit is rated50 - 600 volts; and c) The circuit is as described in (1) - (3).
Report Reference No.: 50337286 001 UL 1012 Clause 20.7 20.8 20.9 20.10 20.11 20.12 21 21.1 Requirement – Test Result – Remark 2) Is ungrounded. With reference to 20.6, the conductor to be grounded shall be one of the output circuit conductors. With reference to 20.6, when the primary circuit to the transformer is derived from the secondary of another transformer, that circuit shall either be: a) Grounded in accordance with 20.9 and 20.10; b) Evaluated as being ungrounded; or c) Ungrounded.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 21.2 Aluminum may be used as a current-carrying part if determined No aluminum used to be acceptable with respect to heating, oxidation, and connection of dissimilar metals. A connection between aluminum and a dissimilar metal in which corrosion can occur shall be evaluated by the heat-cycling test specified in the Standard for Wire Connectors, UL 486A-486B.
Report Reference No.: 50337286 001 UL 1012 Clause 22.2 22.2.1 22.2.2 22.2.3 22.3 22.3.1 22.3.2 22.3.3 22.3.4 22.3.5 22.3.6 22.3.7 Requirement – Test Result – Remark c) Supplementary insulation equivalent to that required by 22.1.1 is provided on each individual conductor. Protection of wiring Internal wiring shall be protected if, when judged in accordance Not accessible with 8.1, it is accessible.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 22.3.8 The means of connecting stranded internal wiring to a wireNo such construction binding screw shall be such that loose strands of wire will be prevented from contacting other live parts not always of the same polarity as the wire, and from contacting dead metal parts.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 23.2.2 A barrier used to provide separation between field wiring of one circuit and field or factory wiring or uninsulated live parts of another circuit shall be spaced no more than 1/16 inch (1.6 mm) from the enclosure walls and interior mechanisms, component-mounted panels, and other parts that serve to provide separated compartments.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 24.1 A barrier or integral part, such as an insulating washer or Insulating material UL bushing, and a base or a support for mounting live parts, shall approved be moisture-resistant material that is not adversely affected by the temperature and stresses to which it is subjected under conditions of use. Insulating material is to be judged with respect to its acceptability for the application.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 26.1.2 A thermal cutoff or other device employed to reduce the risk of fire or electric shock due to overheating of a transformer during abnormal operation shall comply with the requirements applicable to such a device in addition to the applicable requirements in this standard.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 26.2.3 A flanged bobbin-wound transformer shall be constructed so as Not flanged bobbin-wound to maintain physical separation between the primary and transformer secondary windings.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 27 27.1 Resistors The assembly of a power resistor such as a wire-wound type No such resistors requiring a separate support shall be prevented from loosening or rotating by means other than friction between surfaces. An assembly employing lock washers may be considered to comply with the requirement in 27.1.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 28.7 A switch provided as part of a power supply shall be acceptable for the maximum potential to ground of the circuit. A nominal 208-volt, single- or 3-phase, or a 120/240-volt, single-phase product is considered to involve a potential to ground of less than 150 volts.
Report Reference No.: 50337286 001 UL 1012 Clause 29.4 29.5 30 30.1 30.2 30.3 30.4 30.5 31 31.1 Requirement – Test Result – Remark Exception: If the power unit has provision for connection of a grounded neutral conductor, individual single-pole circuit breakers are acceptable as the protection for each ungrounded conductor of a3-wire single phase circuit or for each ungrounded conductor of a 4-wire, 3-phase circuit, provided that no conductor involves a potential to ground in excess of 150 volts.
Report Reference No.: 50337286 001 UL 1012 Clause 31.2 31.3 31.4 31.5 Requirement – Test Result – Remark Exception No. 1: Overcurrent protection is not required to be provided for an output where the current is limited to not more than 110 percent of the receptacle rating by construction of a transformer, one or more resistors, or a regulating network complying with 54.8.1. Exception No.
Report Reference No.: 50337286 001 UL 1012 Clause 31.6 31.7 31.8 31.9 31.10 31.11 32 32.1 Requirement – Test Result – Remark Verdict Exception No. 2: A stationary unit having an input ac attachment plug that has both, a current and voltage rating not exceeding the current and voltage rating of any of the output ac receptacles, need not be provided with overcurrent protection. Exception No.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 32.2 A medium-base screw-shell lampholder shall not be used in a circuit involving a potential of more than 150 volts. 33 33.
Report Reference No.: 50337286 001 UL 1012 Clause 35.1.2 Requirement – Test Result – Remark Exception No. 2: The spacing requirements of 35.1.1 shall not apply to the area between adjacent foils on printed-wiring boards provided with a conformal coating complying with the requirements in the Standard for Polymeric Materials - Use in Electrical Equipment Evaluations, UL 746C. Exception No.
Report Reference No.: 50337286 001 UL 1012 Clause 35.1.3 35.1.4 35.1.5 35.1.6 35.1.7 35.1.8 35.1.9 35.1.10 35.1.11 35.1.12 35.1.13 Requirement – Test Result – Remark e) The encapsulant temperature during the Temperature Test of Section 42 does not exceed 65°C (117°F) rise [based on an assumed operating ambient rating of 25°C (45°F)] or 90°C (194°F) limit (when tested at an ambient rating of greater than 25°C).
Report Reference No.: 50337286 001 UL 1012 Clause 35.1.14 35.2 35.2.1 35.2.2 35.2.3 35.2.4 35.2.5 35.3 Requirement – Test Result – Remark a) The VA or voltage within the circuit is limited to200 VA or 100 volts by a regulating network complying with the requirement in 36.12; or b) A fuse or other overcurrent-protective device, other than an automatically reset type, having a current rating in amperes not exceeding (100VA)/(Vmax), where Vmax is the maximum rms voltage of the secondary in question.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 35.3.1 An insulating liner or barrier of material such as vulcanized fiber or thermoplastic used in lieu of required spacings specified in Exception No. 1 to 35.1.1 shall not be less than 0.028 inch (0.71 mm) thick. The material shall not be used as the sole support of uninsulated live parts involving a risk of fire, electric shock, or electrical-energy/high current.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 35.3.5 a) The wrap is not less than0.013 inch (0.33 mm) thick, is applied in two or more layers, and is used in conjunction with not less than one-half the required through air spacing; b) The wrap is not less than0.028 inch (0.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 36.8 When the control circuit specified in 36.5 is not limited as to available short-circuit current by the construction of a transformer, and the circuit includes either one or more resistors, a fuse, a nonadjustable manual-reset protective device, or a regulating network (see 36.12), the circuits in which the current is limited, in accordance with 36.9, 36.10, or 36.11, is not required to be investigated.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test Result – Remark b) Audibility is capable of being used as a trouble indicator for an electrical supervision circuit; c) A field strength of3 volts per meter (0.91 volts per foot) is to be used for the Radiated EMI Test; and d) Exposure Class H5 is to be used for the Humidity Test. N/A N/A N/A 37 Accessible Signal Circuits 37.1 The requirements in 37.2 and 37.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test Result – Remark 38.2 When an output is marked or otherwise identified as being Class 3, and the output is ac supplied from a linear transformer, that output shall comply with the construction, performance, and marking requirements described in the Standard for Low Voltage Transformers - Part 1: General Requirements, UL 5085-1, and the Standard for Low Voltage Transformers - Part 3: Class 2 and Class 3 Transformers, UL 5085-3.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test Result – Remark MARKING 61 Details 61.1 Cautionary markings See labels 61.1.1 A cautionary marking shall be prefixed by the word "CAUTION," "WARNING," or "DANGER " in letters not less than 1/8 inch (3.2 mm) high. The remaining letters shall not be less than 1/16 inch (1.6 mm) high. 61.1.2 A live heat sink or other part shall be marked "CAUTION - Risk of Electric Shock. Plates (or other word describing the type of part) are live.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 61.1.7 There shall be a legible and durable marking for each interchangeable fuse as described in 30.3, indicating the ampere rating and the voltage rating of the fuse to be used for replacement. The marking shall be located so that it is obvious as to which fuse or fuseholder the marking applies. A single marking is acceptable for a group of fuses.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 61.1.14 A cautionary marking to instruct the operator shall be visible and legible to the operator during the intended operation of the power unit. With reference to the Exception to 7.6.6, a marking shall be located adjacent to the part being guarded to indicate that the cover or guard is to be replaced before operation of the power unit.
Report Reference No.: 50337286 001 UL 1012 Clause 61.2.3 61.2.4 61.2.5 61.2.6 61.2.7 61.2.8 61.2.9 61.2.10 61.2.11 Requirement – Test Result – Remark c) Equipment intended to operate from either direct- or alternating-circuit supplies shall bear markings indicating that the supply may be either direct current or alternating current. The symbol illustrated in Figure 61.3 may be used for this marking.
Report Reference No.: 50337286 001 UL 1012 Clause 61.2.12 61.2.13 61.2.14 61.2.15 61.2.16 61.2.17 61.2.18 Requirement – Test Result – Remark a) The power unit is intended to be permanently connected electrically; and b) The input conductors and the equipment-grounding conductor intended for such connection, with the conductor ampacity based on125 percent of the input rating of the power unit, would not be smaller than that specified in 61.2.12(a) or 61.2.12(b). Exception No.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 61.2.19 With reference to 23.3.2, a unit that relies on the installing electrician to maintain the 1/4 inch (6.4 mm) spacing associated with Class 2 or Class 3 conductors shall be marked with the following or equivalent: "Dress ___ circuits at least 1/4 inch away from ___ circuits," where the blanks are to be completed appropriately with power, light, or Class 1 and Class 2 or Class 3, respectively.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test 62.1.3 Multiple-voltage equipment intended for permanent connection to the branch circuit supply shall be marked to indicate the particular voltage for which it is set when shipped from the factory. The marking shall be on a paper tag or other equivalent nonpermanent material.
Report Reference No.: 50337286 001 UL 1012 Clause 62.1.10 62.1.11 62.2 62.2.1 62.2.2 62.2.3 62.2.4 Requirement – Test Result – Remark a) An insulated grounding conductor that is identical in size, insulation material, and thickness to the grounded and ungrounded branch-circuit supply conductors except that it is green with or without one or more yellow stripes is to be installed as part of the branch circuit that supplies the unit or system.
Report Reference No.: 50337286 001 UL 1012 Clause Requirement – Test Result – Remark 62.2.5 The headings for the user assembly, operation, maintenance, moving and storage, and important safety instructions, and the opening statements of the instructions specified in 61.2.11 "IMPORTANT SAFETY INSTRUCTIONS " and "SAVE THESE INSTRUCTIONS " - shall be entirely in upper case letters not less than 3/16 inch (4.8 mm) high or emphasized to distinguish them from the rest of the text.
Report Reference No.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test 4 4.1 4.2 4.2.1 4.2.2 4.2.3 Constructions Electrical Components and Equipment Enclosures General Thickness of Sheet Metal Enclosures for Live Parts Thickness of Cast Metal Enclosures for Live Parts Complied with impact test Minimum thickness of metal for cast enclosures shall comply with Table 3.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test Result – Remark 4.2.5.6 If a portion of a vertical side panel falls within the area D of the No openings in Enclosures required bottom enclosure as traced out by the 5°angle in Figure 5, that portion of the vertical panel shall be evaluated as a bottom enclosure. 4.2.5.7 If a barrier is provided to comply with Clause 4.2.5.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test Result – Remark 4.2.5.12 Components that have a flammability classification of, at least, No openings in Enclosures HB and that form part of the enclosure need not comply with Clause 4.2.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test 4.2.6.7 A live heat sink for a solid-state component (eg, one mounted No Doors, Covers, and on a printed circuit board), a live relay frame, and the like, that Guards may pose a shock or energy hazard or be mistaken for an unenergized part shall be guarded to reduce the risk of unintentional contact by service personnel or be marked in accordance with Clause 5.1 4.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test 4.5.3 Field wiring provisions for PCE intended for field connection of conductors larger than No. 10 AWG need not include wiring terminals, provided that (a) the PCE is provided with instructions in accordance with Clause 5.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test 4.7.5 Wiring other than that of printed circuits shall consist of wire of a type or types that are suitable for the particular application when considered with respect to (a) conductor size (consideration shall be given to the effects of vibration, impact, and handling for wires smaller than No.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test 4.11.4 Provision shall be made for the safe discharge of the energy stored in capacitors if the safety of an area to which a service worker has access for routine maintenance is dependent upon de-energization of the PCE, unless (a) the covers by which access is gained require the use of tools for removal; and (b) the PCE is marked with clear instructions specifying the time required for a safe discharge (see Clause 5.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test Result – Remark 4.16 Spacings Line Voltage to isolated circuit: Thourgh air and oversurface measured: min 6.6mm. Live part to enclosure: min 7.2mm 4.17 4.18 Alternative approach to spacings Separation of Circuits 4.19 4.20 4.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test 4.22.7 A battery shall be so located and mounted that the terminals of cells will be prevented from coming in contact with the terminals of adjacent cells, or with the metal parts of the battery compartment, as the result of shifting of the battery. .
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test 4.24.2 Clauses 4.24.2 to 4.24.11 apply to all types of liquid preservation systems; Clause 4.24.12 applies to conservator tank systems; Clause 4.24.13 applies to sealed tank systems; and Clause 4.24.14 applies to nonsealed tank systems. Liquid Level 4.24.3 4.24.4 4.24.5 4.24.6 4.24.7 4.24.8 4.24.9 4.24.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test 4.24.11 A pressure-relief device shall be supplied on tanks and liquidfilled compartments that are subjected to pressure in the event of abnormal or fault conditions (such as an arcing fault). This device may be a pressure-relief vent for use on transformers equipped with a conservator tank or a self-resealing mechanical relief device.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 5.10 Requirement – Test Result – Remark (l) For liquid-filled equipment, identification of the dielectric liquid used and quantity in litres. (m) For disconnect switches identification of … (n)Where relevant for safety,the functions … Markings shall comply with the requirements of CSA standard CAN/CSA-C22.2 No.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause 5.11 5.12 5.13 5.14 5.15 5.16 5.17 5.18 5.19 5.20 Requirement – Test Result – Remark (2)This marking may be on a paper tag inside the equipment or equivalent. Notwithstanding clause 5.18.2 of CAN/CSA-C22.2 No.0, PCE for floor mounting that do not conform wIth clause 4.2.5.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test 5.21 When required by clause 4.22.13, the following marking or equivalent shall be provided adjacent to the batteries: CAUTION: RISK OF ELECTRIC SHOCK. BATTERY CIRCUIT IS NOT ISOLATED FROM AC CIRCUIT. HAZARDOUS VOLTAGE MAY EXIT BETWEEN BATTERY TERMINALS AND GROUND. TEST BEFORE TOUCHING. Explicit battery safety instructions (see clause 5.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.1 Clause Requirement – Test Result – Remark 5.29 Verdict When required by clause 4.4.2.7(C), a PCE having a rating of 208V, single phase, and an output receptacle or cord connector rated 250V shall be marked with the following or equivalent marking: CAUTION: OUTPUT OF THIS POWER SUPPLY IS RATED AT 208V AC. 5.
Report Reference No.: 50337286 001 CSA C22.2 No. 107.