The uplink interval is the interval of LoRaWAN data is uploaded
each time. In periodic mode, the uplink interval is equal to the
collection interval.
Range: 30~3600 seconds
Interface I1 Threshold
The threshold mode greatly increases power consumption and is
not recommended.
Value = “Y”, it is the value calculated by Y= Ax+B.
You can choose one of the four rules.
For example, set the uplink interval = 60 min, collection interval
=30s, interface I1 rule is value20.
Datalogger collects data on port I1 every 30 seconds. The collected
data matches the rules. If the value is greater than 20, the data is
uploaded immediately. If the threshold rule is not triggered within 60
minutes, data will be uploaded once every 60 minutes.
When the threshold is triggered and data is uploaded, the Data
Logger will not collect and upload data for 5 minutes. There is
silence for 5 minutes.
Interface I2 Threshold
6.5.1 Set the 0~10V Voltage sensor