Response 014SenseCAPONE3.01019906922104001<CR><LF>
Description
Response the device information
accccccccmmmvvvxxxxxxxxxxxxxxxx<CR><LF>
a Device address: 0
14 SDI-12 protocol version :v1.4
cccccccc Product:SenseCAP
mmm Device series:ONE
vvv Software version:3.0
xxxxxxxxxxxxxxxx
Device serial number:1019906922104001
Modify device
address
0Ab!
Send 0A1!
Response 1<CR><LF>
Description Device address 0 is changed to 1. The address range is 0-9、A-Z、a-z.
Start Measurement
0M!
Send 0M!
Response
Immediately response:00024<CR><LF>
After 2s, the response device’s address, means finishing the measurement.:0<CR><LF>
Description
This command is to start THPL measurement, in order: air temperature, air humidity, atmospheric
pressure, illuminance, but the sensor will not reply to the measurement data immediately after
receiving this command, but the time required to reply the measurement data and the number
of measurements. To obtain measurement data, you must wait until the measurement is
completed, and then use the send data command “0D0!” to obtain it.
After using this command, the sensor will enter a sleep mode after the measurement to save
power consumption. After using "continuous measurement command 0R0!...0R9!", it will exit the
low power consumption state.
The response format is defined as follows:
atttn<CR><LF>
a Device address:0
ttt The time expense to measure data, the unit is
seconds.
n The number of measurements
Extended
Measurement
0M1!...0M9!
Send 0Mn!(n ranges 0~9)
Response
Immediately response:00024<CR><LF>
After 2s, the response device’s address, means finishing the measurement.:0<CR><LF>
Description
0M1!: Start Wind measurement: minimum wind direction, maximum wind direction, average
wind direction, minimum wind speed, maximum wind speed, average wind speed.
0M2!: Start Rain measurement: accumulated rainfall, accumulated rainfall time, rainfall
intensity, maximum rainfall intensity.
0M3!: Start Dust measurement: PM2.5, PM10.
0M9!: Start other measurements: heating temperature, tilt status.