Manual

Manual No. 016-3001-003 249
Flow Meter Extension Cables
Before starting this test, disconnect the flow meter cable from the flow meter. Hold the flow meter cable so that
the keyway is pointing in the 12 o’clock position as shown below.
Pin Designations and Voltage Readings
The following tables show the following pin designations and voltage readings.
Note: In a non-CAN system if a +5 voltage reading is not present, disconnect the Speed Sensor cable. If
the voltage reading is restored, test the Speed Sensor cable as described in Speed Sensor Cable
section on page 247.
Testing the Flow Meter Cable
1. Press Product Control.
2. Press the Product Control Settings area.
Pin Location Designation
2 o'clock Ground
10 o'clock Power
6 o'clock Signal
Pin Connections Voltage
2 o'clock to 6 o'clock +5 Volts
10 o'clock to 2 o'clock +5 Volts
Keyway
10 o’clock
2 o’clock
6 o’clock