Owner's manual

Chapter 11
196 Seed Hawk™ Viper Pro™ Installation & Operation Manual
CAN Troubleshooting
Although the control algorithm is located within the CAN node, all of the same troubleshooting techniques that
you use in a traditional hard-wired system still apply to a CAN system. CAN allows for modularization of the
control system, but the behavior of the system remains the same. Flow and speed sensors, as well as the
control valve and section valves, are used in the same fashion.
Below are some common causes for communication failures:
Issue Possible Cause Solution
CANbus cannot
read the product
node
The node is not
connected to the CANbus
Connect the node and re-initialize the Viper console to
read the product node.
CANbus ends not
terminated
Terminate CANbus ends
Make sure that both ends of the CANbus system are
properly terminated. See Chapter 2 for more
information. Note: The first terminator is built into the
Seed Hawk
®
switch box mounted in the cab.