7.4.6 TROUBLESHOOTING
1.MUXSensorisnotrecognizedatpowerup.Thiswillincludethegroundspeed,fan,andbin
levelsensors
Possible causes: Harness wiring is faulty or the sensor is
defective.
Solution: Withthe system turnedon, go thesensorthatisnot
communicating. There is a LED on each sensor (except the
multilevel bin sensor). If it is flashing slowly (1 flash every 23
seconds) that indicates that power and ground are connected
but the sen sor wire is not. The power wire is +12 volt s and is
the white wire. It is in the “A” position on the connector. The
Ground wire is black and is in the “B” position on the
connector. The sen sor wire is the green wire and is in the “C”
positionontheconnector.IftheLEDisnotflashing,unplugthe
sensor from the harness and plug it back in. If the LED lights
momentarily, power is present and the sensor is faulty. If the
LED does not light at all check power at the connector. You
should measure 12 volts between the white and black wire. If
youdo,thesensorisfaulty,ifyoudon’ttheharnessisfaulty.All
thewhite wires on theMUXharnessare connected in parallel,
alltheblackwiresareinparallel,andallthegreenwiresarein
parallel.Youcanmeasurecontinuitybe‐tweenany ofthe“A”,
“B”,or“C”connectionsontheMUXharness.