User Manual
SEDONA BY LYNX™ VENT HOOD CARE & USE/INSTALLATION 
|
5
a) Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes 
 and standards, including fire-rated construction codes and standards.
b) Sufficient air is needed for proper combustion and exhausting of gasses through the flue (chimney) of fuel       
 burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guidelines and safety         
 standards such as those published by the National Fire Protection Association (NFPA) and the American Society 
 for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) and the local code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
d) Ducted fans must always be vented to the outdoors.
e) For safe and secure wall mounting, the Sedona by Lynx™ Vent Hood should be mounted to a solid vertical surface 
 of sufficient width to allow for mounting of the Hood. The horizontal surface should extend from a vertical plane 
 to the point directly in front of the exhaust roof cap (or wall cap).
f) The Hood should be installed with a MINIMUM of three (3) feet of weather proof roof coverage on all sides that 
 are not protected from direct rain by an adjacent wall.
g) It is also required that all duct work and roof openings be thoroughly sealed with the applicable tape and/or roof 
 sealant to prevent ingress of water.
INSTALLING THE VENT HOOD
WARNING
To Reduce The Risk Of Fire, Electric Shock, Or Injury To Persons, Observe The Following:
WARNING
To Reduce The Risk Of Fire, Use Only Metal Ductwork. To reduce the risk of fire and to properly exhaust air, 
be sure to duct air outside – Do not vent exhaust air into spaces with in walls or ceilings or into attics, crawl 
spaces, or garages.
1.  For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2.  To reduce the risk of fire and to properly exhaust air, the hood must be exhausted to outside air. Never exhaust into 
a wall, an attic or a concealed area in the building. This can create a potential hazard.
3.  Consult a licensed ventilation contractor or qualified technician for proper installation of exhaust ducting. 
4.  Locate the cooking area for minimum cross drafts.
5.  Ducts must be of adequate size and duct runs should be as short as possible. Where turns are necessary, keep 
turning radius as large and as smooth as possible.
6.  The ducting must be air tight. Use a minimum of 2 sheet metal screws at every duct joint. Then, seal the duct joints 
with high quality duct tape.
7.  Only use ductwork constructed of materials deemed acceptable by state, municipal and local codes. 
8.  Plan the installation so that all minimum clearances are met or exceeded. Dimensions shown provide   
minimum clearances, unless otherwise specified. 










