Installation manual
INSTALLATION MANUAL AND USERS GUIDE
Multi Split Series – Ductless Split – Cassette Indoor unit
04006030101 © Sedna Aire Europe GmbH 17 02/2014
The raise should be formed with rectangular angles not exceeding a height of 280 mm
The hose shall be hung up at rods hanging from the ceiling at a distance of 1-1,5 m by using the clamps
Insert the hose into the clamp and tighten the clamp
Isolate the drain hose against the clamp
Isolate the hose AND the surrounding clamp against condensation
When you install more cassettes, connect the drain hose serial from the highest to the lowest that always
a negative slope downwards exists
Drain hose
Drain hose
Clamp
Ceiling
Correct
Wrong
Clamp
Isoalting sheet
Drain hose
Isoalting sheet
Clamp
> 100 mm
1% slope