Specifications

MR-2320 Series Installation and Operation Manual
71
How the Panel Works in Mode 10
Activation of either Z-1 or Z-2 turns NAC-1 on steady.
Activation of either Z-1 or Z-2 turns NAC-2 on at 60BPM. Release Timer-1 is started.
Expiration of Release Timer-1 activates both RAC-1 and RAC-2. NAC-1 and NAC-2 turn on steady.
Activation of Z-6 starts Manual Release Delay Timer -1(MDT-1). Upon the expiration of MDT-1, both RAC-1 and
RAC-2 are active. NAC-1 and NAC-2 turn on steady.
If Z-5 is active, Release Timer-1 is held and NAC-2 is downgraded from 60BPM to 20 BPM.
Releasing of Z-5 resumes Release Timer-1 and NAC-2 goes back to 60BPM. Release Timer-1's value depends
on Abort Delay Type.
Activation of Z-3 turns both NAC-1 and NAC-2 on steady.
Activation of Z-4 can be indicated on NAC-2 at Temporal, if configured.