Specifications
Pre-Programmed Modes
70
Mode 10: Agent Release, Single Hazard, Not Cross-zoned, Combined Release
Zone Configuration
• Detection Zone -1: Alarm (Hazard Area1, not cross-zoned)
• Detection Zone -2: Alarm (Hazard Area1, not cross-zoned)
• Detection Zone -3: Alarm (Pressure Switch or Water-flow)
• Detection Zone -4: Supervisory
• Detection Zone -5: Abort Switch
• Detection Zone -6: Manual Release
• NAC -1: Signal, will be activated steady when there is any alarm zone active.
• NAC -2: Signal, indicate the Hazard Area1 status.
• RAC 1: Releasing Circuit
• RAC -2: Releasing Circuit
Hazard Configuration
• Default Release Timer Value: 60 seconds
• Default Manual Release Delay: 0 seconds.
• Default Abort Delay Type: Standard UL.
• Soak Timer Value: 0 seconds (continuous)
NAC Configuration
• Default Escalating NAC code of Hazard Area State:
• Hazard Idle: Off
• Hazard Alert: 20BPM
• Hazard Alarm: 60BPM
• Hazard Release: Steady
• Default NAC code of supervisory is Temporal
Detection Zones Phantom Zones Release Timers
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 Zp2
RT1
Exp
RT2
Exp
Alm Alm WF Supv AB MR Z1+Z2 Z3+Z4
Out1 Signal Steady XXX X
Out2 Signal Escalating X(X) X X
Out3 Rel. Releasing XX
Out4 Rel. Releasing XX
RLS TMR 1 Started X
RLS Tmr 1 Interrupted X
RLS Tmr 1 Cancelled X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled