Specifications

Pre-Programmed Modes
68
Mode 9: Agent Release, Single Hazard, Cross-zoned, NYC abort
Zone Configuration
Detection Zone -1: Alarm (Hazard Area 1, cross-zoned)
Detection Zone -2: Alarm (Hazard Area 1, cross-zoned)
Detection Zone -3: Alarm (Pressure Switch or Water-flow)
Detection Zone -4: Supervisory
Detection Zone -5: Abort Switch
Detection Zone -6: Manual Release
NAC-1: Escalating Signal, indicate Hazard Area 1 status.
NAC-2: Escalating Signal, indicate Hazard Area 1 status, Supervisory Optional.
RAC-1: Releasing Circuit (Hazard Area 1)
NAC-3: Silenceable Strobe.
Hazard Configuration
Default Release Timer Value: 60 seconds
Default Manual Release Delay: 0 seconds
Default Abort Delay Type: NYC
Default Soak Timer Value: 0 seconds (continuous)
NAC Configuration
Default Escalating NAC code of Hazard Area State:
Hazard Idle: Off
Hazard Alert: Steady
Hazard Alarm: 120BPM
Hazard Release: Steady
Default NAC code of supervisory is 20 BPM
Detection Zones Phantom Zones Release Timers
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 Zp2
RT1
Exp
RT2
Exp
Alm Alm WF Supv AB MR Z1+Z2 Z3+Z4
Out1 Signal Steady X
Out2 Signal Escalating X(X) X X
Out3 Rel. Releasing XX
Out4 Strobe Steady XXX X
RLS TMR 1 Started X
RLS Tmr 1 Interrupted X
RLS Tmr 1 Cancelled X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled