Specifications
Pre-Programmed Modes
68
Mode 9: Agent Release, Single Hazard, Cross-zoned, NYC abort
Zone Configuration
• Detection Zone -1: Alarm (Hazard Area 1, cross-zoned)
• Detection Zone -2: Alarm (Hazard Area 1, cross-zoned)
• Detection Zone -3: Alarm (Pressure Switch or Water-flow)
• Detection Zone -4: Supervisory
• Detection Zone -5: Abort Switch
• Detection Zone -6: Manual Release
• NAC-1: Escalating Signal, indicate Hazard Area 1 status.
• NAC-2: Escalating Signal, indicate Hazard Area 1 status, Supervisory Optional.
• RAC-1: Releasing Circuit (Hazard Area 1)
• NAC-3: Silenceable Strobe.
Hazard Configuration
• Default Release Timer Value: 60 seconds
• Default Manual Release Delay: 0 seconds
• Default Abort Delay Type: NYC
• Default Soak Timer Value: 0 seconds (continuous)
NAC Configuration
• Default Escalating NAC code of Hazard Area State:
• Hazard Idle: Off
• Hazard Alert: Steady
• Hazard Alarm: 120BPM
• Hazard Release: Steady
• Default NAC code of supervisory is 20 BPM
Detection Zones Phantom Zones Release Timers
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 Zp2
RT1
Exp
RT2
Exp
Alm Alm WF Supv AB MR Z1+Z2 Z3+Z4
Out1 Signal Steady X
Out2 Signal Escalating X(X) X X
Out3 Rel. Releasing XX
Out4 Strobe Steady XXX X
RLS TMR 1 Started X
RLS Tmr 1 Interrupted X
RLS Tmr 1 Cancelled X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled