How the Panel Works in Mode 7
Activation of either Z-1 or Z-2 changes Hazard Area 1 state into Alert. NAC-1 turns on at Temporal.
Activations of both Z-1 and Z-2 change Hazard Area 1 state into Alarm. Release Timer-1 is started. Upon the
expiration of Release Timer-1, RAC-1 is active. NAC-1 turns on steady.
Activation of either Z-3 or Z-4 changes Hazard Area 2 state into Alert. NAC-2 turns on at Temporal.
Activations of both Z-3 and Z-4 changes Hazard Area 2 state into Alarm. Release Timer 2 is started. Upon the
expiration of Release Timer 2, RAC-2 is active. NAC-2 turns on steady.
Activation of Z-6 turns both NAC-1 and NAC-2 steady.
Activation of Z-5 can be indicated on NAC-2, if enabled.