Specifications

Pre-Programmed Modes
64
Mode 7: Pre-action/Deluge, Dual Hazard, Cross-zoned, Split Release
Zone Configuration
Detection Zone -1: Alarm (Hazard Area 1, cross-zoned)
Detection Zone -2: Alarm (Hazard Area 1, cross-zoned)
Detection Zone -3: Alarm (Hazard Area 2, cross-zoned)
Detection Zone -4: Alarm (Hazard Area 2, cross-zoned)
Detection Zone -5: Supervisory
Detection Zone -6: Water-flow.
NAC -1: Escalating Signal, indicates Hazard Area 1 status
NAC -2: Escalating Signal, indicates Hazard Area 2 status
RAC -1: Releasing Circuit (Hazard Area 1)
RAC -2: Releasing Circuit (Hazard Area 2)
Hazard Configuration
Default Release Timer Value: 0 seconds
Default Manual Release Delay: 0 seconds (not used)
Default Abort Delay Type: Standard UL (not used)
Default Soak Timer Value: 0 seconds (continuous)
NAC Configuration
Default Escalating NAC code of Hazard Area State:
Hazard Idle: Off
Hazard Alert: Temporal
Hazard Alarm: 120BPM
Hazard Release: Steady
Default NAC code of Supervisory is 20 BPM.
Detection Zones Phantom Zones Release Timers
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 Zp2
RT1
Exp
RT2
Exp
Alm Alm Alm Alm Supv WF Z1+Z2 Z3+Z4
Out1 Signal Steady XX
Out2 Signal Escalating XX
Out3 Rel. Releasing X
Out4 Rel. Releasing X
RLS TMR 1 Started X
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled
RLS Tmr 2 Started X
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled