Specifications
MR-2320 Series Installation and Operation Manual
63
Mode 6: Pre-action/Deluge, Single Hazard, Not Cross-zoned, Combined Release
Zone Configuration
• Detection Zone -1: Alarm (Hazard Area 1, not cross-zoned)
• Detection Zone -2: Alarm (Hazard Area 1, not cross-zoned)
• Detection Zone -3: Alarm (Hazard Area 1, not cross-zoned)
• Detection Zone -4: Alarm (Hazard Area 1, not cross-zoned)
• Detection Zone -5: Supervisory
• Detection Zone -6: Water-flow.
• NAC -1: Signal, steady on any alarm.
• NAC -2: Supervisory optional.
• RAC -1: Releasing Circuit (Hazard Area 1)
• RAC -2: Releasing Circuit (Hazard Area 1)
Hazard Configuration
• Default Release Timer Value: 0 seconds
• Default Manual Release Delay: 0 seconds (not used)
• Default Abort Delay Type: Standard UL (not used)
• Default Soak Timer Value: 0 seconds (continuous)
NAC Configuration
• Default Escalating NAC code of Hazard Area State:
• Hazard Idle: Off
• Hazard Alert: Temporal
• Hazard Alarm: Temporal
• Hazard Release: Steady
• Default NAC code of Supervisory is 20 BPM.
How the Panel Works in Mode 6
• Activation of any one among Z-1, Z-2, Z-3 and Z-4 changes Hazard Area 1 state into Alarm. Release Timer-1 is
started. NAC-1 turns on at Temporal. Upon the expiration of Release Timer-1, NAC-1 turns on steady. RAC-1
and RAC-2 are activated.
• Activation of Z-5 can be indicated on NAC-2 at 20 BPM, if configured.
• Activation of Z-6 turns NAC-1 steady.
Detection Zones Phantom Zones
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 RT1 Exp
Alm Alm Alm Alm Supv WF Z1+Z2+Z3+Z4
Out1 Signal Steady XXXX X
Out2 Signal Escalating (X)
Out3 Rel. Releasing X
Out4 Rel. Releasing X
RLS TMR 1 Started XXXX
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled