Specifications

Pre-Programmed Modes
62
Mode 5: Pre-action/Deluge, Single Hazard, Cross-zoned, Combined Release
Zone Configuration
Detection Zone -1: Alarm (Hazard Area 1, cross-zoned)
Detection Zone -2: Alarm (Hazard Area 1, cross-zoned)
Detection Zone -3: Alarm (Hazard Area 1, cross-zoned)
Detection Zone -4: Alarm (Hazard Area 1, cross-zoned)
Detection Zone -5: Supervisory
Detection Zone -6: Water-flow Alarm.
NAC -1: Signal, will be activated if there is any alarm zone active.
NAC -2: Escalating Signal, indicates Hazard Area 1 status, Supervisory Optional.
RAC -1: Releasing Circuit (Hazard Area 1)
RAC -2: Releasing Circuit (Hazard Area 1)
Hazard Configuration
Default Release Timer Value: 0 seconds
Default Manual Release Delay: 0 seconds (not used)
Default Abort Delay Type: Standard UL (not used)
Default Soak Timer Value: 0 seconds (continuous)
NAC Configuration
Default Escalating NAC code of Hazard Area State:
Hazard Idle: Off
Hazard Alert: Temporal
Hazard Alarm: 120 BPM
Hazard Release: Steady
Default NAC code of Supervisory is 20 BPM.
How the Panel Works in Mode 5
Activation of Z-1, Z-2, Z-3 or Z-4 changes Hazard Area 1 state from Idle to Alert. NAC-1 turns on steady. NAC-2
sounds Temporal.
Activations of any two of Z-1, Z-2, Z-3 and Z-4 change Hazard Area 1 state into Alarm. Release Timer-1 is
started. NAC-2 turns on at 120 BPM. Upon the expiration of Release Timer 1, both RAC-1 and RAC-2 turn on.
NAC-1 and NAC-2 turn on Steady
Activation of Z-6 turns on both NAC-1 and NAC-2 steady.
Activation of Z-5 is indicated on NAC-2 at 20 BPM, if configured.
Detection Zones Phantom Zones
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 RT1 Exp
Alm Alm Alm Alm Supv WF Z1+Z2+Z3+Z4
Out1 Signal Steady XXXX X
Out2 Signal Escalating (X) X
Out3 Rel. Releasing X
Out4 Rel. Releasing X
RLS TMR 1 Started X
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled