Specifications

Pre-Programmed Modes
60
Mode 4: Agent Release, Dual Hazard, Not Cross-zoned, Split Release
Zone Configuration
Detection Zone -1: Alarm (Hazard Area 1, not cross-zoned)
Detection Zone -2: Alarm (Hazard Area 1, not cross-zoned)
Detection Zone -3: Alarm (Hazard Area 2, not cross-zoned)
Detection Zone -4: Alarm (Hazard Area 2, not cross-zoned)
Detection Zone -5: Abort/Manual Release Combination (hazard 1)
Detection Zone -6: Abort/Manual Release Combination (hazard 2)
NAC -1: Escalating Signal, indicates Hazard Area 1 state
NAC -2: Escalating Signal, indicates Hazard Area 2 state
RAC -1: Releasing Circuit (Hazard Area 1)
RAC -2: Releasing Circuit (Hazard Area 2)
Hazard Configuration
Default Release Timer Value: 60 seconds
Default Manual Release Delay: 0 seconds.
Default Abort Delay Type: Standard UL.
Default Soak Timer Value: 0 seconds
NAC Configuration
Default Escalating NAC code of Hazard Area State:
Hazard Idle: Off
Hazard Alarm: Temporal
Hazard Release: Steady
How the Panel Works in Mode 4
Activation of either Z-1 or Z-2 changes Hazard Area1 state from Idle to Alarm. NAC-1 turns on at Temporal.
Release Timer-1 is started.
Detection Zones Phantom Zones Release Timers
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 Zp2
RT1
Exp
RT2
Exp
Alm Alm Alm Alm AB/MR AB/MR Z1+Z2 Z3+Z4
Out1 Signal Steady XX X
Out2 Signal Escalating XX X
Out3 Rel. Releasing XX
Out4 Rel. Releasing XX
RLS TMR 1 Started XX
RLS Tmr 1 Interrupted X
RLS Tmr 1 Cancelled X
RLS Tmr 2 Started XX
RLS Tmr 2 Interrupted X
RLS Tmr 2 Cancelled X