Specifications

Pre-Programmed Modes
56
Mode 2: Agent Release, Single Hazard, Not Cross-zoned, Combined Release
Zone Configuration
Detection Zone -1: Alarm (Hazard Area 1, not cross-zoned)
Detection Zone -2: Alarm (Hazard Area 1, not cross-zoned)
Detection Zone -3: Alarm (Water-flow or pressure switch)
Detection Zone -4: Supervisory (default non-latching)
Detection Zone -5: Abort Switch
Detection Zone -6: Manual Release
NAC-1: Signal, will be on steady if there is any alarm zone or manual release switch active.
NAC-2: Signal, indicates the cadence of hazard area 1 state or supervisory circuit (optional).
RAC-1: Releasing Circuit (Hazard Area 1)
RAC-2: Releasing Circuit (Hazard Area 1)
Hazard Configuration
Default Release Timer Value: 60 seconds
Default Manual Release Delay: 0 seconds.
Default Abort Delay Type: Standard UL.
Default Soak Timer Value: 0 seconds
NAC Configuration
Default Escalating NAC code of Hazard Area State:
Hazard Idle: Off
Hazard Alert: Temporal
Hazard Alarm: Temporal
Hazard Release: Steady
Default NAC code of Supervisory Signal is 20 BPM.
Detection Zones Phantom Zones Release Timers
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 Zp2
RT1
Exp
RT2
Exp
Alm Alm WF Sup AB MR Z1+Z2 Z3+Z4
Out1 Signal Steady XXX X
Out2 Signal Escalating X(X) X
Out3 Rel. Releasing XX
Out4 Rel. Releasing XX
RLS TMR 1 Started XX
RLS Tmr 1 Interrupted X
RLS Tmr 1 Cancelled X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled