Specifications
Pre-Programmed Modes
54
Pre-Programmed Modes
Mode 1: Agent Release, Single Hazard, Cross-zoned, Combined Release
Zone Configuration
• Detection Zone -1: Alarm (Hazard Area1, Cross-zoned)
• Detection Zone -2: Alarm (Hazard Area1, Cross-zoned)
• Detection Zone -3: Alarm (Pressure Switch or Water-flow)
• Detection Zone -4: Supervisory (Non-latching by default)
• Detection Zone -5: Abort Switch
• Detection Zone -6: Manual Release Switch
• NAC-1: Signal, will be on steady if there is any alarm zone or manual release switch active.
• NAC-2: Signal, indicates the cadence of hazard area 1 state or supervisory circuit (optional).
• RAC-1: Releasing Circuit (Hazard Area 1)
• RAC-2: Releasing Circuit (Hazard Area 1)
Hazard Configuration
• Default Release Timer Value: 60 seconds
• Default Manual Release Delay: 0 seconds.
• Default Abort Delay Type: Standard UL.
• Default Soak Timer Value: 0 seconds
Detection Zones Phantom Zones Release Timers
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 Zp2
RT1
Exp
RT2
Exp
Alm Alm WF Sup AB MR Z1+Z2 Z3+Z4
Out1 Signal Steady XXX X
Out2 Signal Escalating X(X) X X
Out3 Rel. Releasing XX
Out4 Rel. Releasing XX
RLS TMR 1 Started X
RLS Tmr 1 Interrupted X
RLS Tmr 1 Cancelled X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled