Specifications

Configuration
48
Command Menu-->Dialer-Config
Time Parameters
Command Menu/Dialer-Config/Report
Options
4. Aux Disc Alm/Supv Rpt.
[ ] ENABLE
[X] DISABLE ->Default
If this function is enabled, the
Aux Disconnect feature
(obtained by pressing the Aux
Disconnect button) will block
the alarm and supervisory
events from being reported
through the built-in dialer.
Note: Refer to How to Use the Keypad to Program the MR-2320 on page 34 for detailed instructions on
making menu selections.
Command Menu/Dialer-Config/Time
Parameter
1. AC Loss delay
0 ->Default
The AC loss delay
ranges from 0 to 20
hours
Use this function to delay the
reporting of AC loss trouble on
the dialer for the programmed
time period. Press UP or
DOWN button to increase or
decrease the number of hours.
Command Menu/Dialer-Config/Time
Parameter
2. Cellular report date
0 ->Default
The cellular report
date ranges from 0 to
28
Use this function to set the test
report date for the cell phone
setup. If the date is set to 0,
this means there is no test
reporting for cell phone or the
phone line is a regular line.
Other settings could be
anywhere from 01-28,
representing which day of the
month the test should be
performed. Press the UP or
DOWN buttons to scroll
through the days.
Command Menu/Dialer-Config/Time
Parameter
3. Auto test time
00:30 ->Default
Use this function to set the
time for auto test. This test has
to be performed once a day to
send the test report to the
monitoring station. The time is
in 24hr format, which means
00:30 is 30 minutes after mid-
night. Press the UP or DOWN
buttons to increase or
decrease the time.
Please do not use the
following test times: 00:00,
01:55, 02:00 and 03:00.
AuxDis Alm/Supv Rpt.
[X] DISABLE
-Time Parameter-
1. AC-Loss Delay
2. Cellphone Date
3. Auto-Test Time
AC-Loss Delay(Hrs)
0
Cellular Report Date
0
Auto-Test (HH:MM):
00:30