Specifications
Configuration
38
Command Menu-->Panel Config-->Features
2. Wtr/Sprk. Retd
[ ] ENABLE
[X] DISABLE->Default
By default all the initiating
circuits configured as waterflow
or sprinkler act as non-verified
alarms. If enabled, a retard
operation is performed for
initiating circuits configured as
waterflow or sprinkler.
Command Menu-->Panel Config-->Features
3. Aux Dis Corr
[X] ENABLE ->Default
[ ] DISABLE
By default this function will
disconnect the auxiliary alarm
relay when the aux disconnect
button is pressed. If enabled,
this function will disconnect the
auxiliary alarm relay
and all
correlated relays when the aux
disconnect button is pressed.
Correlated relays include:
MR-2306-R6 and MR-2312-
S12.
Command Menu-->Panel Config-->Features
4. Sig-Sil Inh Tmr
[X] DISABLE->Default
[ ] 10sec
[ ] 20sec
[ ] 30sec
[ ] 1min
Use this function to inhibit the
signal silence switch for a
desired length of time. The time
period should expire before the
signals may be silenced.
According to the Canadian
National Building Code, this
timer should be set to one
minute.
Command Menu-->Panel Config-->Features
5. Aux. Dis. Dis Alam&Sv
[ ] ENABLE
[X] DISABLE->Default
If enabled the Common Alarm
and Common Supervisory
relays will be disconnected
when Aux. Disconnect is
pressed. Also, the MR-2300-PR
will not transmit a supervisory or
alarm event.If disabled, the Aux
disconnect switch has no effect
on the Common Alarm relay, the
Common Supervisory relay, and
the MR-2300-PR.
Command Menu-->Panel Config-->Features
6. Auto Sig-Sil. Tmr
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 20 Min
[ ] 30 Min
Use this function to set the time
period for which the indicating
circuits will sound before they
are automatically silenced.
According to the Canadian
National Building Code, this
timer should not be set to less
than 20 minutes.
Command Menu-->Panel Config-->Features
7. Rem. Annun.
[X] NONE->Default
[ ] 1
[ ] 2
...
[ ] 6
Use this function to program the
number of remote annunciators.
Any combination of remote
annunciators or smart relays
can be used as long as the
number does not exceed 6. The
annunciators’ addresses should
be linear: without gaps and in
sequence.
Command Menu-->Panel Config-->Features
8. Alarm Xmit-Sil.
[ ] ENABLE
[X] DISABLE->Default
Use this function to allow the
alarm transmit and auxiliary
alarm relay to reset on the
Signal Silence rather than the
Reset switch.
Waterflow/Sprk Retd
[X] DISABLE
Aux Dis. Dis Corr
[X] ENABLE
Sig-Sil. Inhibit Timer
[X] DISABLE
Aux Dis. Dis Alm&Sv
[X] DISABLE
Auto Sig-Sil. Tmr
[X] DISABLE
No. of Remote Annun.
[X] NONE
Alm Xmit-Sil.
[X] DISABLE