Specifications

MR-2320 Series Installation and Operation Manual
37
Command Menu-->Panel Config-->Features
Command Menu-->Panel Config-->
Hazard Config
4. Soak timer
0->Default (continuous)
The selectable values are
in seconds: 0, 10, 20, 30,
40, 50, 60, 120(2min),
180(3min), 240(4min),
300(5min), 360(6min),
420(7min), 480(8min),
540(9min), 600(10min),
660(11min), 720(12min),
780(13min), 840(14min),
900(15min)
Use this function to set the
length of time for which the
releasing circuit is active. When
the soak timer expires, the
control panel automatically
shuts off the activated releasing
circuit.
0 seconds means that the soak
timer is disabled and the
releasing circuit is active
continuously.
Note: Refer to How to Use the Keypad to Program the MR-2320 on page for detailed instructions on
making menu selections.
Command Menu-->Panel Config-->Features
1. Manual Sig. Silence
[X] ENABLE ->Default
[ ] DISABLE
Use this function to enable or
disable the Signal Silence
operation on the panel.
Soak timer(sec):
0
-Panel Features-
1. Man. Sig. Sil
2. Wtr/Sprk. Retd
3. Aux Dis Corr
4. Sig-Sil Inh Tm
5. Aux Dis Alm&Sv
6. Auto Sil. Tmr
7. Rem. Annun.
8. Alm. Xmit. Sil.
9. Pwr Fail Tmr.
10. Com. Supv. Rly
11. Sig. Sil. Isol.
12. 1st Alarm Code
13. 2nd Alarm Code
14. Supv. Latching
15. Supv on NAC-2
16. Sig-Sil NAC
Man. Sig. Sil.
[X] ENABLE