Specifications

Configuration
36
Command Menu-->Panel Config-->Hazard Config
Note: Refer to How to Use the Keypad to Program the MR-2320 on page for detailed instructions on
making menu selections.
Command Menu-->Panel Config-->
Hazard Config
1. Release Timer
60->Default
Available options:
0,5,10,15,20,25,30,35,40,
45,50,55,60 seconds
Use this function to set the
programmable timer that delays
the activation of the releasing
application circuits.
This timer starts immediately
after receiving a confirming
alarm (cross-zoned hazard
area) or a single alarm (non-
cross-zoned hazard area).
When the timer expires, the
releasing circuit activates.
Value: 0 to 60 seconds in five-
second increments.
Command Menu-->Panel Config-->
Hazard Config
2. Abort Delay
[X] Standard UL->Default
[ ] IRI
[ ] NYC
[ ] Local Juris.
Use this function to set how the
Abort Switch operates with the
Release Timer.
Note that if the Release Timer is
set to zero, the Abort Switch
does not operate.
In
Standard UL mode, the
release timer will stop and hold
when the Abort Switch is
pressed. When the switch is
released, the Release Timer
restarts from whichever is
greater: the remaining time on
the timer or 10 seconds.
In
IRI mode, the switch works in
the same way as it does in
Standard UL mode, except that
the switch will function only if it
is pressed and held before the
second alarm comes in.
In
NYC mode, pressing the
Abort Switch will reset to the
Release Timer and add 90
seconds to the configured timer
duration. After the Abort Switch
is released, the Release Timer
will restart.
In
Local Juris. (Local
Jurisdiction Delay), pressing the
Abort Switch will reset the
Release Timer back to its
configured value. After the
switch is released, the Release
Timer will restart.
Command Menu-->Panel Config-->
Hazard Config
3. Man. Rls Delay
0->Default
Available options:
0, 5, 10, 15, 20, 25, 30
seconds
Use this function to set the time
delay of activation of
corresponding releasing
circuit(s) after activation of the
manual release switch.
Value: 0 to 30 seconds in five-
second increments.
-Hazard Param.-
1. Release timer
2. Abort Delay
3. Manual Rls Delay
4. Soak timer
Release timer(sec):
60
Abort Delay Type:
[X] Standard UL
Man. Rls Delay(sec):
0