Indicators, Controls and Operations
28
Menu Buttons
To use the menu buttons you will need to install the CFG-300 configuration tool. See Using the CFG-300 Tool on
page for details.
Switches and Common Indicators
The MR-2320 Series panel is a six-zone panel with four output circuits. The circuits are arranged in the following
configuration:
Zone 1 Input circuit
Zone 2 Input circuit
Zone 3 Input circuit
Zone 4 Input circuit
Zone 5 Manual Release/Abort switches combination or individual switch
Zone 6 Manual Release/Abort switches combination or individual switch
Out 1 NAC1
Out 2 NAC2
Out 3 Releasing circuit 1
Out 4 Releasing circuit 2 or NAC3 in some applications
Zone 1 to Zone 4
• Alarm LED (red) turns on steady when an alarm is detected
• Supervisory LED (amber) turns on steady when the circuit is active
• Trouble LED (amber) turns on at slow flash rate when in trouble or bypassed
Zone 5 and Zone 6
• Alarm LED & Trouble LED The zone type and LED behavior varies upon the configuration. Steady when
turned on.
Out1 and Out2 (NAC circuits)
• Trouble LED (amber) turns on at slow flash rate when in trouble or bypassed
Out3 and Out4 (Releasing circuits)
• Trouble LED (amber) turns on steady when the circuit is bypassed
turns on at slow flash rate when in trouble
Input Circuits Bypass Switch
These bypass switches are used to bypass the input circuit. Bypass is a toggle switch which will bypass and un-
bypass in a sequence whenever the switch is pressed. When the input circuit is bypassed a trouble is generated and
the system will not respond to any trouble or alarm on the bypassed input circuit. If the bypassed input circuit is
active and the Bypass Switch is pressed for un-bypassing, the Alarm LED will flash at the fast rate for 10 seconds.
During these 10 seconds, pressing the Bypass Switch can bypass the active input circuit again. After 10 seconds,
the bypassed alarm will be processed.
Menu Button
Pressing and entering the passcode will allow you to enter the command menu.
Info Button
When the system is off-normal, press to display extra information of the event.
Enter Button
Pressing this button to select a menu option or to confirm a menu operation.
Cancel Button
To return to previous menu in the configuration or command mode.
M
M
?
?
X