Specifications
MR-2320 Series Installation and Operation Manual
17
Figure 11: Abort and Manal Release Switch Class A or Style D Wiring
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5
DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
Current limiter
MP-1500R/W
MANUAL RELEASE
SWITCH
USE MS-403,404
USE ONLY NO
CONTACT
ABORT SWITCH
CCONNECT A UL/ULC LISTED ABORT STATION
ACCEPTABLE TO THE AHJ, COMPLYING WITH THE
FOLLOWING SPECIFICATIONS:
MAXIMUM IMPEDENCE = 1.4K OHMS
RATED CURRENT = 45mA
RATED VOLTAGE= 24V
Abort and Manual Release switches on a combined circuit
Abort and Manual Release switches on separate circuits
Current limiter
MP-1500R/W
Note: Maximum 4 Abort
Switches can be connected
on each combined Manual
Release and Abort Switch circuit.
Current limiter
MP-1500R/W
Current limiter
MP-1500R/W
BLK RED
BLK RED
-DET5 OUT+-DET6 OUT+
-DET5 RET+-DET6 RET+
BLK RED
BLK RED
-DET5 OUT+-DET6 OUT+
-DET5 RET+-DET6 RET+
MR-2300-A
CLASS A
CONVERTER
MODULE
MR-2300-A
CLASS A
CONVERTER
MODULE