Unit installation
DIP Switch Settings
4
DIP Switch Settings
Each annunciator needs to be assigned a unique, sequential address via DIP switches SW1-1, SW1-2, and 
SW1-3. DIP switch SW1-4 is used to allow disabling of some front panel slide switches.
Set the annunciator address (see the manual for the fire alarm control panel being used), as follows in the 
table below:
Annunciators on a common RS-485 connection must be numbered sequentially; i.e.: 1,2,3,4, and not 
randomly such as 5,3,7. Note that not all annunciator “addresses” are valid for all fire alarm control panels. 
Refer to the fire alarm control panel manual for further information.
Jumper Selection
Jumper JP1 connects pins 2 and 3 and thus provides an eight bit checksum.
JW4
Jumper Intact = Buzzer silence & Lamp Test local function only. System Reset & Signal Silence are 
disabled.
Cut Jumper to have all remote functions operate.
SW1-1 = Address A0\
>
Three digit address of the annunciator (address 
range 1 to 7 inclusive)
SW1-2 = Address A1
SW1-3 = Address A2/
SW1-4 = 
When SW1-4 is “off”, the System Reset and Signal Silence slide-switches are 
always disabled, regardless of the operation of the keyswitch. The Buzzer 
Silence and Lamp Test slide-switches will operate with the use of the 
keyswitch.
When SW1-4 is “on”, all four slide -switches on the front panel will operate 
with the use of the keyswitch. 
Annunciator 
Address
SW1 DIP Switch Settings
SW1-1 SW1-2 SW1-3
1ONOFFOFF
2 OFF ON OFF
3ONONOFF
4OFFOFFON
5ONOFFON
6 OFF ON ON
7ONONON