Installation manual
11
Specifications and Features
5.0 Specifications and Features
5.1 Enclosure
• A standard 4-gang electrical box is used.
5.2 Electrical Specifications
• 24 VDC nominal voltage
• Slide-switch controls, LED indicators, and keyswitch to enable controls.
• Local buzzer, indicators (ac-on, common trouble, signal silence), and controls (system
reset, lamp test, buzzer silence, signal silence).
• Annunciation of up to 16 points.
• Not expandable.
• Standby 35 mA Max., All LED’s illuminated 140 mA max.
5.3 Current Drain for Battery Calculations
The lamp test feature draws the maximum normal current because it illuminates all lamps on
one chassis at a time. Thus the currents are:
Use the “normal standby current” for battery size calculations (see the fire alarm control panel
manual for battery calculations) and includes the current drain for the Trouble Buzzer, Trouble
LED, and one alarm LED. Use the “maximum current” to calculate the wire size (see the
wiring instructions on page 10).
5.4 Environmental Specifications
This annunciator is intended for indoor use only.
Normal Standby
Current = 35 mA
Maximum Current
= 140 mA