User guide
Table Of Contents

MR-2100/2200 Programming Manual
61
* Call directions: A/R = alarm/restoral; T/R = trouble/restoral; MA/R = maintenance alarm/restoral; S/R =
supervisory/restore; T = test transmission
** Line number/telephone number is identified (XX)
Table 2: Contact ID Zone Alarm/Restore Event Codes
Program any of these codes for zone alarms/restorals when using the standard (i.e. not automatic)
Contact ID reporting format:
Table 3: SIA Format Automatic Zone Alarm/Restore Codes
ZZZ = zones 01-250, 256
Walk Test Start/
Stop
control panel has entered/exited walk
test mode; no
events will be communicated
MA/R (6) A7 TS-000/
TE-000
Test
Transmission
Normal/
Off-Normal
test transmission reports system
normal or off-normal (alarm,
supervisory or trouble) control panel
condition
T (6) A2 RP-000/
RY-000
Medical Alarms (1)18 Near Alarm 24 Hour Non Fire
(1)A1 Emergency Panic Alarms (1)51 Gas Detected
(1)A2 Fail to Report In (1)2A Panic (1)52 Refrigeration
Fire Alarms (1)21 Duress (1)53 Loss of Heat
(1)1A Fire Alarm (1)22 Silent (1)54 Water Leakage
(1)11 Smoke (1)23 Audible (1)55 Foil Break
(1)12 Combustion General Alarms (1)56 Day Trouble
(1)13 Water Flow (1)4A General Alarm (1)57 Low Bottled Gas Level
(1)14 Heat (1)4A General Alarm (1)58 High Temp
(1)15 Pull Station (1)43 Expansion module failure (1)59 Low Temp
(1)16 Duct (1)44 Sensor tamper (1)61 Loss of Air Flow
(1)17 Flame (1)45 Module Tamper
Zone
Definition
Alarm/Rest Rep.
Codes*
Supervisory/Rest. Rep.
Codes*
Trouble/Rest. Rep.
Codes*
Fire FA-ZZZ/FH-ZZZ FS-ZZZ/FR-ZZZ FT-ZZZ/FJ-ZZZ
Sprinkler SA-ZZZ/SH-ZZZ SS-ZZZ/SR-ZZZ ST-ZZZ/SJ-ZZZ
Heat KA-ZZZ/KH-ZZZ KS-ZZZ/KR-ZZZ KT-ZZZ/KJ-ZZZ
Water WA-ZZZ/WH-ZZZ WS-ZZZ/WR-ZZZ WT-ZZZ/WJ-ZZZ
Untyped UA-ZZZ/UH-ZZZ US-ZZZ/UR-ZZZ UT-ZZZ/UJ-ZZZ
Reporting Code Code sent when...
Dialer
Direction*
Contact
ID Auto
Rep.
Codes
SIA Auto
Rep.
Codes