User guide

MR-2100/2200 Programming Manual
47
Zone Number
PPP:ZZ.SSS Format:
PPP Control Panel Number
ZZ Panel Zone
Notes:
1. These zones do not restore.
2. Privilege Level 0 generates a restore signal; all others generate a trouble signal.
3. This zone does not restore and is not repeated sequentially in the archive.
4. Programs dated before March 4, 1996 use a different numbering sequence. Panels
updated erase the archive the first time the new program runs.
Panel
Zone
Description
Panel
Zone
Description
0 General Alarm
80
2
Privilege Level
1 Initiating Circuit 1 81 1st Stage Alarm
2 Initiating Circuit 2 82 2nd Stage Alarm
50 Network Verify 83 Switch
51 Comlink 1 84 Test Mode
52 Comlink 2
85
1
Erase Configuration
53 Comlink 3
86
3
Change Configuration
54 Comlink 6 87 Passcode Tamper
56 MRDL/City-Tie
88
1
Database Loaded
60 Output (bell/releaser) Supervision
89
1
Time/Date Change
61 Auxiliary Power Supervision
90
1
Hot Key Activation
64
1
Program Checksum
91
1
Memory Overflow
65
1
Database Checksum
92
1
Network Reboot
66 AC Power
93
1
New Program
67 Low Battery
94
1
Network Reboot Required who
69
1
Program Restart
95
1
Network Reboot Required why
70 Battery Charger