MR-2100/2200 Programming Manual
40
Figure 26: Selector Screen
For all screens, <Clear> returns to the previous menu level without changing any information and
<Home> returns to the Main Menu without changing any information.
3.3 Menus
Clock Menu
This menu has the following options:
• Date: View or change the date. The date is entered in MM.DD.YY format. Each section of
the date must be separated by a dot. Press <Enter> to accept date typed. <Clear>
removes any digits typed. If no digits are displayed, <Clear> returns you to the Clock
Menu. The new date is sent to all other panels on the Network, if used. All panels assume
this date. The date change is recorded in the Archive.
• Time: Change the time. The time is entered in HH.MM.SS format. Each section of the
time must be separated by a dot. All times are in 24 hour format. Press <Enter> to accept
time typed. <Clear> removes any digits typed. If no digits are displayed, <Clear>
returns you to the Clock Menu. The new time is sent to all other panels on the Network, if
used. All panels assume this time. If <Enter> is pressed with no time entered, the current
time is sent to all panels on the network. If a change of greater than 5 minutes occurs, the
new time is recorded in the archive.
• Calibrate: Calibrates the clock so that it keeps correct time. Calibration takes 2 to 45
days. Waiting longer gives more accurate results. The panel functions normally while
calibrating. When sufficient time has passed, re-selecting this function asks for the correct
time. The calibration is then be reported. In a network, only the master panel needs to
calibrated.
Common Relays Menu
This function is restricted to Privilege Level 2. The menu has the following options:
• Disconnect: View or change the relays that can be disconnected by the Common
Disconnect hot key. Selected relays are marked by an asterisk (*). To change the
selection, move the cursor to the desired relay A(larm), S(upervisory) or T(rouble) and
press <Enter> to change. Select OK when done. <Clear> returns you to Program Menu
without making changes.
• Test Inhibit: View or change whether common relays are disconnected during Test Mode
or not. <Clear> returns you to Program Menu without making changes.
Note: 1. The Master Panel in a network synchronizes all clocks in the network at 03:30 every day,
sending both date and time.
2. Changing the time while the panel is calibrating aborts the calibration.
Note: Changing the time using the Time option aborts the calibration. If a panel is currently in a
calibration, it ignores time changes sent over the network.
Title
Options
Selections
COMMON DISCONNECT
A S T
* - * OK<