User guide

MR-2100/2200 Programming Manual
31
Circuits Window. Unused circuits are shown using three dashes. Use the <Backspace> key in
order to quickly re-position the current selection to another circuit. The <Up> and <Down> Arrow
keys change the current circuit. The <Right> and <Left> Arrow keys change the type of the
current circuit. The <Plus> and <Minus> keys change the function of the current circuit.
Circuit Type Selector
The Circuit Type Selector is
located below Circuit List on the
left hand side. It is shown on the
Circuit Window only. It is a drop
down box used to assign the
current circuit type. If the circuit is
unused, select not assigned.
Only options supported by the
Input Circuit Modules
programmed for the current panel
are assignable.The Device List is
located in the top left corner of
the window. It is shown on the
Devices Window only. It lists any
defined addressable devices for
the current addressable circuit,
the two entries for a dual end-of-line circuit, and the separate smoke detector and n/o contract
device for a Smoke Detector + N/O Contact circuit. For addressable devices, the type of device
and its function are shown for each one. Unused addresses are shown with three dashes. Use the
<Backspace> key in order to quickly re-position the current selection to another device. The
<Up> and <Down> Arrow keys change the current device. The <Right> and <Left Arrow>
keys will change the type of the current device. The <Plus> and <Minus> keys will change the
function of the current device.
Device Type Selector
The Device Type Selector is located below Device List on the left hand side. It is shown on the
Device Window only. It is a drop down box used to assign the current device type. Ion, Photo,
Thermal, Acclimate, Dual Acclimate, or Laser. For addressable circuits, it displays all the sensors
or modules that can be programmed for the current device address, sensors for addresses 1 to 99
and modules for addresses 101 to 199. If the address is unused, select not assigned. The
following module types are available:
Monitor (Class B): This is a standard monitor module using Class B (Style B) wiring and
an end-of-line resistor. This must be chosen for MRI-M500DM, MRI-M501M and MRI-
M503M modules.
Monitor (Class A): This is a standard monitor module using Class A (Style D) wiring. This
can be used only with the MRI-M500M and MRI-M502M modules.
Control (supervising): This programs the MRI-M500S for use as a generic signalling
circuit. It can be turned on by alarm or supervisory inputs. It will remain on until the system
is reset.
Control (relay): This is used for programming the MRI-M500R relay module.
Control (Bell): This programs the MRI-M500S as a standard signalling circuit. It will turn
on continuously when activated by an alarm. They will silence when the Signal Silence
button is pressed. It does not sound codes.
Note: Both devices listed for Dual end-of-line and Smoke Detector + N/O Contact circuits must be defined.
Figure 21: Devices Window