User guide

MR-2100/2200 Programming Manual
28
The Test Transmission Cycle determines the number of days between test transmissions. This is
automatically set so that tests are performed daily and may not be varied.
The TLM Trouble Delay controls the number of telephone line monitoring checks required before a
telephone line trouble is generated. The dialer checks the telephone connection at 10-second
intervals.
The Maximum Dialing Attempts to Each Phone Number is the number of attempts that the dialer
will make to each telephone number before generating a fail to communicate trouble.
Post Dial Wait for Handshake is the amount of time the dialer will wait for a valid initial handshake
from the receiver after dialing the programmed telephone number.
Call Directions
The Call Directions dialog (see
Figure 16) contains the options that
determine which telephone
numbers will be used to
communicate events.
There are five different types of
events that can each be sent to
telephone number one or telephone
number two. The event types are
Fire Zone Alarm/Restore,
Supervisory Zone Alarm/Restore,
Zone Trouble/Restore, Maintenance
Trouble/Restore and Test
Transmissions.
Zone Data
The Zone Data dialog (see Figure 17) contains zone definitions and reporting codes that the dialer
will use to communicate events.
Note: If an upgraded database has a value other than 1, choose Set Default to reset the value.
Note: UL Listing requires that the Test Transmission be sent to both telephone numbers
Figure 16: Call Directions