MR-2100/2200 Programming Manual
24
Second Stage
Inhibit
Prevents the automatic operation of second stage operation. This applies only to
panels with ALERT or STAGED type bell systems. For ALERT systems, pressing the
Second Stage Inhibit will prevent the panel from going into second stage. For STAGED
systems, it will prevent the system from going to the next stage. Second Stage Inhibit
has no effect on an EVAC type bell system. The green LED will flash when Second
Stage Inhibit is available, and the yellow LED will flash when it has been activated.
Fire Drill Activates all the bell circuits, both regular and coded, in Alert mode. Press a second
time to have all bell circuits sound in Evacuation mode. Press a third time to end the
Fire Drill. The yellow LED will flash while the Fire Drill is happening. The Fire Drill
cannot be performed if the bells are already activated, or if AC power is off. The Fire
Drill is automatically ended if an alarm condition occurs.
Releaser
Disconnect
Causes the releaser circuits to ignore any new alarms. The buzzer beeps every 2
seconds while the releasers are disabled. This beeping is suppressed while a
privileged level is entered in the panel. Press again to restore normal operation. The
yellow LED will flash while active. If no releasers can be disconnected, Releaser
Disconnect will do nothing. This function can be set to Privilege Level 0 or 1.
Relay
Disconnect
Causes the function relays and control modules to ignore any new alarms. Press again
to restore normal operation. The yellow LED will flash while active. If no relays nor
control modules can be disconnected, Relay Disconnect will do nothing. This function
can be set to Privilege Level 0 or 1.
Test Mode Places panel into test mode. Press again to return to normal mode. The yellow LED
will flash while in test mode. This function can be set to Privilege Level 0 or 1. It follows
the Disconnect privilege level (set in MHI). During test mode, the remote annunciator
zone LEDs becomes non-latching for the zone(s) under test. The common indicators,
bells, relays and releasers are not activated and no commands are sent to other units
and no signal is sent out of Port 3. Test signals can be archived or not as required.
Before beginning testing, the circuits/devices to be tested must be selected. All
unselected circuits/devices will operate normally. Be sure that the panel is in test
mode. To select circuits/devices, select PROGRAM from the Main Menu on the LCD.
The arrow keys move the cursor and the <Enter> key selects the item. Then select
ADDRESSABLE, then TEST. Enter the device circuit and address for each device to
be tested. <Clear> will return to the previous menu.
When test mode is ended, all zones and devices selected for testing automatically
return to normal operation.
Note: There is no Ground Fault isolation while Test Mode is active.
Signal
Disconnect
Disables sounding of the bells. The buzzer beeps every 2 seconds while the bells are
disabled. This beeping is suppressed while a privileged level is entered in the panel.
Press Signal Disconnect again to re-enable the bells. The yellow LED will flash while
the bells are disabled. Signal Disconnect is not available if the bells are already
activated. This function can be set to Privilege Level 0 or 1.
Common
Disconnect
Disables the municipal relays from functioning. Press again to enable relays. The
yellow LED flashes while the relays are disabled. The municipal relays affected are
programmable. If no relays are selected for disabling, Common Disconnect is
unavailable. This function can be set to Privilege Level 0 or 1.
Key Action